SIMPLEX PACKAGED PUMP SETS (SPS/SKS SERIES)
MECHANICAL OPTIONS

Other options: Control Devices and Alarms, Level Controllers, Gauges, and Fill Controllers, Duplex Pump Systems, and Pumps and Motors
 

NO.

DESCRIPTION

015
Auxiliary hand pump, piston type, 20 gallons per 100 strokes. Self-primes to 6 meters (20 feet) of lift. (1" NPT)

060
Fuel Strainer
a) For use with standard 2–5 GPM pumps
b) For use with optional 7-25 GPM pumps (options 400-428)
c) For use with pumps larger than 25 GPM (options 428-432)

062
Duplex strainer with selector valve. No break transfer. Inactive strainer may be removed for cleaning.
a) 1” NPT
b) 1½” NPT
c) 2” NPT

070
Check valve
a) For use with 2–17 GPM pumps
b) For use with option 417; 25 GPM pump and larger

080
Solenoid valve. For AC systems. Specify voltage.
a) ½” NPT, for use with standard 2 GPM pump or option 420, 422: 3, 5 GPM pumps
b) ¾” NPT, for use with option 400, 410, 415: 7, 10, 17 GPM pumps
c) 1” NPT
d) 1¼” NPT, for use with option 417: 25 GPM pump
e) 2” NPT

083
Solenoid valve, as above, for DC systems. Specify voltage.
a) ½” NPT
b) ¾” NPT
c) 1" NPT

087
Manual shut-off valve, ball type
a) ½", bronze
b) ¾", bronze
c) 1", bronze
d) 2", bronze
e) 3", bronze

088
Manual shut-off valve, ball type
a) ½", fire rated
b) ¾", fire rated
c) 1", fire rated
d) 2", fire rated
e) 3", fire rated

089
Needle valve, 1"

093
Fusible link valve, self-closing when acted upon by 165°F or greater. Supplied loose for remote installation or installed on tank as specified.
a) 1½” NPT
b) 2" NPT
c) 3" NPT

095
Pressure relief valve.
a) For use with standard 2 GPM pump or option 420, 422: 3, 5 GPM pumps
b) For use with option 400, 410, 415: 7, 10, 17 GPM pumps
c) For use with option 417: 25 GPM pump

097
Back-pressure regulating valve.
a) 1” NPT
b) 1½” NPT

100
Pressure gauge with isolation hand valve, installed on pump outlet; oil filled
a) 2"
b) 4"

101
Vacuum gauge with isolation hand valve, installed on pump inlet; oil filled
a) 2"
b) 4"

103
Flow gauge, in line with pump, to 30 GPM
104 Ball motion flow indicator
105 Temperature gauge
106 Stainless steel braided flex hose
107 Vibration isolator set

181
Weatherproof Modification, SPS-only.
a) SPS-10
b) SPS-25
c) SPS-55

191
Leak sensor (standard N/C for SPS/SKS containment sump)


SIMPLEX PACKAGED PUMP SETS (SPS/SKS SERIES)
CONTROL DEVICES AND ALARMS OPTIONS

Other options: Mechanical, Level Controllers, Gauges, and Fill Controllers, Duplex Pump Systems, and Pumps and Motors
 

NO.

DESCRIPTION

260
Disconnect switch with door interlock for main power inlet connection. Guarded terminals for line connections, pad lockable handle mechanism interlocked to prevent opening of door until switch is turned “Off.”

261
“On-Off” system circuit breaker with short circuit trips.
a) Single pole
b) Three pole

262
50VA, 480/240: 120, single phase, control power transformer

271
Pilot light

281
“Pump Run-Off-Automatic” operation mode selector switch. (For option 345: Duplex Pump Systems, order two.)

285
Loss of flow alarm. Sensor detects fuel flow from pump and activates alarm if flow is lost while pump is running.
Adjustable sensitivity and time delay. (For option 345: Duplex Pump Systems, order two.)
286 Differential pressure switch for fuel strainer

298
Control Relay. Plug-in type. 3 PDT, 10A, 240V AC, 115V AC or 24V DC

334
Alarm horn


SIMPLEX PACKAGED PUMP SETS (SPS/SKS SERIES)
LEVEL CONTROLLERS, GAUGES, AND FILL CONTROLLERS OPTIONS

Other options: Mechanical, Control Devices and Alarms, Duplex Pump Systems, and Pumps and Motors

NO.

DESCRIPTION

212
Digital level indicator, 115 VAC, for local or remote installation

212-A
Nema 4X wall-mount enclosure

213
Digital level indicator with 4-20mA output

2010
Simplex SST Analog Level Controller including 5-point level indicator, differential pump control (pump-in or pump-out), low level alarm/contacts, high level alarm/contacts, high level override shut-off, pump h-o-a switch, pump test push-button, power available indicator, pump running indicator. Can be used with duplex pump controller, Option #345. Includes transmitter assembly for installation in remote tank, requires 4" fitting. Specify tank depth

2011
Simplex PLC Level Controller, used in conjuction with Option 349 PLC based duplex pump controller, including 5-point level
indicator, differential pump control (pump-in or pump-out), low level alarm/contacts, high level alarm/contacts, high level
override shut-off, pump h-o-a switch, pump test push-button, power available indicator, pump running indicator. Can be used
with duplex pump controller, Option #345. Includes transmitter assembly for installation in remote tank, requires 4" fitting.
Specify tank depth

2015
Option for SST level controller: tank leak sensor and alarm. Includes leak sensor float switch or optical sensor. Specify dimensions.

2016
Nema 3R wall-mount enclosure

2017
Nema 1 wall-mount enclosure


SIMPLEX PACKAGED PUMP SETS (SPS/SKS SERIES)
DUPLEX PUMP SYSTEMS OPTIONS

Other options: Mechanical, Control Devices and Alarms, Level Controllers, Gauges, and Fill Controllers, and Pumps and Motors
 

Duplex pump options are used to increase the reliability of a pumping system through the addition of a second, backup pump and level control. In a duplex system, one pump is designated the “lead” pump and the other is the “lag” pump. The lead pump automatically refills the tank over the tank’s normal operating range of 50% to full. Normally, once the tank has been initially filled, the fuel level should never drop below 50%. Less than 50% is indicative of either a failure of the lead pump or consumption in excess of pump capacity. The lag pump and its separate level controller, acting as a backup senses a drop in fuel level below 50% and starts the lag pump, which then continues to run, along with the lead pump, until the tank is full.

When ordering, remember that duplex systems include two motor-pumps and therefore require a quantity of two of any option related to the motor or pump, such as valves, strainers, etc.

NO.

DESCRIPTION

345
Multifunction duplex pump controller system providing selectable operating modes, including:

1) Automatic lead pump alternating with automatic lag pump backup
2) Manual lead pump selection, automatic alternating, automatic lag pump backup
3) Automatic twin pump operation (both pumps run simultaneously) automatic level control backup
4) Manual operation

Basic System includes the following:

1) Mode selector switch
2) Pump running indicators for each pump
3) Two 1/3HP, 120V, 2GPM pumps, with check valves

285
Sensor to detect pump flow and indicate failure of pump. Use with duplex pump controller to start lag pump and activate alarm. (Order two for option 345: Duplex Pump Systems.)

346
Running time meter, one for each pump. (Order two for option 345: Duplex Pump Systems.)

347
Manual duplex pump selector switch. Used to select one of two pumps or both pumps for automatic operation. In single pump mode, off-line pump not available for automatic operation. Includes:

1) Selector switch with positions “pump-1,” “pump-2,” “both”
2) Pump running lights
3) Two 1/3 HP, 120 V, 2 GPM pumps, with check valves

349
Basic PLC based duplex controller


SIMPLEX PACKAGED PUMP SETS (SPS/SKS SERIES)
PUMPS AND MOTORS OPTIONS

Other options: Mechanical, Control Devices and Alarms, Level Controllers, Gauges, and Fill Controllers, and Duplex Pump Systems

Note: The following optional pumps and motors are in lieu of basic unit.
The 2 GPM Super-XL pump and the 1/3 HP, 230V AC, single-phase, 60 Hertz motor are the standard pump and motor provided with the basic unit.
Pump capacity at 1725 RPM. 50 Hz operation reduces capacity to 83%.
 

NO.

DESCRIPTION
Super-XL Pumps
High-tech hydraulic pump featuring pressure-loaded, self-compensating gears and a mechanical shaft seal designed for applications where the pump starts and stops on demand. For more information click here.

400
7 GPM pump in lieu of 2 GPM basic unit pump. Requires a ½ HP motor not included in price. (¾” NPT)

410
10 GPM pump in lieu of 2 GPM basic unit pump. Requires a ¾ HP motor not included in price. (¾” NPT)

415
17 GPM pump in lieu of 2 GPM basic unit pump. Requires a 1 HP motor not included in price. (¾” NPT)

417
25 GPM pump in lieu of 2 GPM basic unit pump. Requires a 1½ HP motor not included in price. (1¼” NPT)
420 Series Pumps
High performance cast iron/steel rotor pump for use with heavy fuel or continuous circulation systems where pump runs virtually nonstop. HP is minimum motor size. For more information click here.

418
1.8 GPM, 1/3 HP

420
3 GPM, ½ HP

422
5 GPM, ¾ HP
500 Series Pumps
High performance cast iron/steel rotor pump for use with heavy fuel or continuous circulation systems where pump runs virtually nonstop. HP is minimum motor size.

501
1 GPM

503
2 GPM

505
3 GPM

510
10 GPM

520
17 GPM

530
25 GPM

540
35 GPM
Motors
3-phase motors may be operated at 190/380V, 50Hz. 50Hz operation reduces pump capacity to 5/6.

605
1/3 HP, 230V AC, single phase, 60 Hertz motor, ODP

615
1/3 HP, 115V AC, single phase, 50 Hertz motor, ODP

616
1/3 HP, 220V AC, single phase, 50 Hertz motor, ODP

621
1/3 HP, 230/460V AC, 3-phase, ODP motor with starter. Specify voltage.

622
1/3 HP, 230/460V AC, 3-phase, TEFC motor with starter. Specify voltage.

630
1/3 HP, 12V DC motor

635
1/3 HP, 24V DC motor

645
1/3 HP, 115V AC, single phase, 60 Hertz motor, TEFC

700
½ HP, 115V AC, single phase, 60 Hertz motor, ODP

705
½ HP, 230V AC, single phase, 60 Hertz motor, ODP

715
½ HP, 110V AC, single phase, 50 Hertz motor, ODP

716
½ HP, 220V AC, single phase, 50 Hertz motor, ODP

721
½ HP, 230/460V AC, 3-phase, ODP motor with starter. Specify voltage.

722
½ HP, 230/460V AC, 3-phase, TEFC motor with starter. Specify voltage.

730
½ HP, 12V DC motor

735
½ HP, 24V DC motor

745
½ HP, 115V AC, single phase, 60 Hertz motor, TEFC

768
Single phase magnetic motor starter with overload relay and control transformer. Includes disconnect switch with short circuit protection. For 115V AC or 230V AC, single phase, motors.

770
3-phase magnetic motor starter with overload relay and control transformer. Includes disconnect switch with short circuit protection. For 230V AC or 460V AC, 3-phase, motors.

800
¾ HP, 115V AC, 60 Hertz, single phase motor, ODP

805
¾ HP, 230V AC, 60 Hertz, single phase motor, ODP

822
¾ HP, 230/460V AC, 60 Hertz, 3-phase motor, TEFC, with motor starter. Specify voltage.

825
¾ HP, 230/460V AC, 60 Hertz, 3-phase motor, with motor starter, ODP. Specify voltage.

845
¾ HP, 115/230V AC, 60 Hertz, single phase motor, TEFC. Specify voltage.

900
1 HP, 115V AC, 60 Hertz, single phase motor, ODP

905 
1 HP, 230V AC, 60 Hertz, single phase motor, ODP

922
1 HP, 230/460V AC, 60 Hertz, 3-phase motor, TEFC, with motor starter. Specify voltage.

925
1 HP, 230/460V AC, 60 Hertz, 3-phase motor, with motor starter, ODP. Specify voltage.

945
1 HP, 115/230V AC, 60 Hertz, single phase motor, TEFC. Specify voltage.

1000
1½ HP, 115V AC, 60 Hertz, single phase motor, ODP

1005
1½ HP, 230V AC, 60 Hertz, single phase motor, ODP

1022
1½ HP, 230/460V AC, 3-phase, 60 Hertz, TEFC, with motor starter. Specify voltage.

1025
1½ HP, 230/460V AC, 3-phase, 60 Hertz, with motor starter, ODP. Specify voltage.

1045
1½ HP, 115/230V AC, single phase, 60 Hertz, TEFC. Specify voltage.

1100
2 HP, 115V AC, 60 Hertz, single phase motor, ODP

1105
2 HP, 230V AC, 60 Hertz, single phase motor, ODP

1122
2HP, 208V AC, 3-phase, 60 Hertz motor, ODP

1125
2 HP, 230/460V AC, 60 Hertz, 3-phase motor with motor starter, ODP. Specify voltage.

1145
2 HP, 115/230V AC, 60 Hertz, single phase motor, TEFC. Specify voltage.

1200
3 HP, 115V AC, 60 Hertz, single phase motor, ODP

1205
3 HP, 230V AC, 60 Hertz, single phase motor, ODP

1225
3 HP, 230/460V AC, 60 Hertz, 3-phase motor with motor starter, ODP. Specify voltage.

1305
5 HP, 230V AC, 60 Hertz, single phase motor, ODP

1322
5HP, 230V AC, 3-phase, 60 Hertz motor, TEFC

1325
5 HP, 230/460V AC, 60 Hertz, 3-phase motor with motor starter, ODP. Specify voltage.

1405
7½ HP, 230V AC, 60 Hertz, single phase motor, ODP

1422
7½HP, 208V AC, 3-phase, 60 Hertz motor, ODP

1425
7½ HP, 230/460V AC, 60 Hertz, 3-phase motor with motor starter, ODP. Specify voltage.