Reliant
Series Systems Fuel Tanks
|
OVERVIEW
High reliability design systems fuel tanks for use as day tanks,
main supply tanks, transfer tanks, return tanks
Integrated, packaged design including tank, gauging, controllers,
pumps
Network compatible with Simplex Fuel Supply System products and
with building management systems
UL142 double-wall tanks
UL2080 double-wall, fire-rated designs
UL2085 double-wall fire rated, protected designs
Filtration tank designs
10-3000 gallons
UL508 digital and analog controllers
Hazardous location constructions available
FEATURES
Double wall tank construction, UL listed
Digital or analog controllers, UL listed
Local or remote pumping options, 2-50GPM, 0.33 5.0HP
Single or duplex, fill or return pumping configurations
Large option and accessory list
Highly standardized and time proven design
Design-build project customization
Digital controllers network compatible
Fully compatible with complete Simplex Fuel Supply Systems product
line, including pump sets, tank filling systems, tank filtration
systems, digital fuel management systems, digital controllers
TANK
CONSTRUCTION
All tanks are UL listed as noted, all-welded steel, atmospheric
design, suitable for outdoor or indoor installation. Tank finish
to 150 gallons is powder-coat white, above 150 gallons white
industrial enamel
Standard duty tanks:
10-400 gallons, UL142 secondary containment construction, rectangular
design,
400-5000 gallons, UL142, double-wall construction, cylindrical
design
Fire-rated duty tanks:
10-400 gallons, UL2080 or UL2085 protected design, double wall
construction, rectangular design
Sales Bulletin
Options |
|
The Simplex SRS Series Reliant
Series comprises a standard line of Systems Fuel Tanks finding
application as day tanks and other tank applications featuring
integration of intelligent control with pumping and gauging systems.
The Reliant Series is a progressive design evolution of the iconic
Simplex Packaged Day Tank Line realizing the latest technology
in tank design and construction and use of advanced digital and
analog control systems. The Reliant Series is fully compatible
for network integration with the full line of Simplex Fuel Supply
Systems, including packaged pump systems, tank filling systems,
filtration systems, digital fuel and tank management systems
and digital monitoring and data systems. The Reliant Series,
when supplied with a Simplex digital controller, is MODBUS and
Ethernet compatible with most tank gauging systems including
Pneumercator, Veeder-Root and Omntec as well as with most Building
Management Systems.
Fuel tanks used with the Reliant Series are UL labeled, double-wall
design, suitable for indoor or outdoor use. Normal duty, rectangular
construction tanks are UL142, closed-top dike construction. Cylindrical
designs are UL142 double-wall construction. Fire-rated designs
are available with UL2080 or UL2085 listings.
Normal duty products are UL508 listed, NEMA1 indoor, NEMA3R,
4, 12 indoor/outdoor. Hazardous location controllers are available.
As a progressive, evolutionary design of the Simplex Pacakged
Day Tank product line, the Reliant Series finds it core application
as a generator day tank. In this traditional application, the
Reliant Day Tank integrates a tank of required capacity with
a level controller and fill control. On-board fill pumps and
return pumps are typical. Remote pumping systems are available
for filling of multiple tanks, management of multiple source
tanks or when required by pipe run or pump size conditions. |
Both digital and analog controllers
are available. Digital controllers are PLC based and network
compatible. Digital controllers utilize both a point-sensing
float switch input and a 4-20mA analog-to-digital input which
displays on a panel indicator and provides a 4-20mA output. Analog
controllers are based upon the time-proven Simplex SST Controller.
Other applications of the Reliant Series include:
|
1. |
Bulk fuel source tanks with pumping
systems to transfer fuel to Reliant Day Tanks or to Generator
Base Tanks |
|
2. |
Transfer tanks |
|
3. |
Return tanks to receive fuel from
Reliant Day Tanks or base tanks and pump back to source tanks
In every case, the Simplex Reliant Series achieves a new level
of reliability. |
In every case, the Simplex
Reliant Series achieves a new level of reliability.
|
1. |
Double-wall tank construction represents
the latest in conservative, space saving design |
|
2. |
Comprehensive hazardous location
and fire rated designs integrate tanks with control, pumping
and valveing systems suitable for the special use intended |
|
3. |
Purpose built systems integration
and network compatibility addresses todays needs for building
and systems automation in a developed, standardized design |
|
4. |
Advanced digital control systems
feature system redundancy and self-checking |
|
5. |
Traditional analog control systems
feature time-proven, conservative design |
The SRM Series Manual
Day Tank provides basic storage only. It includes a manual
fuel fill port and a mechanical level gauge. The standard SRM
package includes a UL142 listed tank. Limited options are available. |
DIGITAL CONTROLLER
|
DRS Digital Controller |
|
UL508 listed |
|
NEMA 1 or NEMA3R enclosed |
|
PLC based |
|
6-inch touch-panel operator interface, monochromatic
standard, color optional |
|
Dual level sensor input: |
|
|
4-20mA continuous sensor, analog-to-digital
input |
|
|
Point sensing float switches: low, refill
start, refill stop, high, plus checkpoint for automatic cross
check of sensors |
|
Leak sensor |
|
Spare I/O for options and design-build features
MODBUS and Ethernet network compatible 4-20mA loop output for
tank level |
|
Operator touch-panel interface functions: |
|
|
HOA switch |
|
|
Test |
|
|
Reset |
|
|
Alarm silence |
|
|
Numeric display of tank level in gallons (liters) |
|
|
Graphic condition display of tank level and
pump/status/alarm condition |
|

|
|
Message indicators for status and alarm, including: |
|
|
|
Normal operation |
|
|
|
Pump running (fill, return, single or multiple
pumps) |
|
|
|
Tank filling |
|
|
|
Low |
|
|
|
Critical low |
|
|
|
High |
|
|
|
Critical high |
|
|
|
Leak |
|
|
|
Not in auto |
|
|
|
Controller failure with specific message |
|
|
|
Other messages as determined by design build
option configuration |
|

|
Relay dry contact outputs for the following
(10A, SPDT): |
|
|
Low alarms |
|
|
High alarms |
|
|
Leak |
|
|
Not in auto |
|
|
Other alarms as determined by design-build
option configuration |
 |
ANALOG LEVEL CONTROLLER
|
Multifunction liquid level controller: |
|
|
Usable with any tank construction |
|
|
Versatile mounting |
|
|
Accessories to suit a multitude of tank level
applications |
|
|
Leak detection capability |
|
|
UL 508A Listed |
|
The Simplex Analog Level Controller is a relay
based design, float switch activated, multifunction liquid level
controller. SST applications include: |
|
|
Single fill pump control |
|
|
Duplex fill pump control, level switch activated |
|
|
Duplex fill pump control, pressure switch
activated |
|
|
Single drain pump control |
|
|
Duplex drain pump control |
|
|
Pump-in, pump-out control |
|

The SST Controller is UL 508A Listed.
The controller is activated by level point sensing float switches. |
|
The standard level transmitter is suitable
for use with class-II flammable liquids or water. Optional level
transmitters are available: |
|
|
Intrinsically safe transmitters for use with
Class I liquids |
|
|
Alloy or plastic materials for use with corrosive
liquids |
|
Consult Simplex for compatibility of materials. |
|
PUMPS
Reliant, SRS Series Fuel
Tank Systems are available with on-board fill and/or return pumps
in single or duplex configuration.
Capacity range is 2-50gpm, 0.33 5.0HP, single or 3-phase.
Simplex SPS or SKS Series Packaged Pump Sets are used remotely
when required by system complexity or pipe-run constraints or
where multiple-tank systems are supplied by common pumps. |
Standard pumps are Parker-Hannifin,
advanced technology, hydraulic gear pumps with self-prime maintenance,
high-lift capability, linear pressure versus flow output. Construction
features machined steel gears, dynamic pressure loaded internal
seals, stainless steel shaft, mechanical shaft seal, cast-aluminum
housing.
Optional pumps are heavy-duty cast iron construction with mechanical
shaft seals.
Motors are industrial NEMA size, conservatively rated. All commercial
voltage ratings available . |

|
|
MODEL NUMBERS |
|
CAPACITY |
RATING |
DAY TANKS |
FILTRATION TANKS |
SPECIALTY TANKS |
|
50 Gallons |
UL142 |
SRS-50 |
SRFT-50 |
SRX-50 |
|
UL2080 |
SRS-50 FR |
SRFT-50 FR |
SRX-50 FR |
|
UL2085 |
SRS-50 PT |
SRFT-50 PT |
SRX-50 PT |
|
75 Gallons |
UL142 |
SRS-75 |
SRFT-75 |
SRX-75 |
|
UL2080 |
SRS-75 FR |
SRFT-75 FR |
SRX-75 FR |
|
UL2085 |
SRS-75 PT |
SRFT-75 PT |
SRX-75 PT |
|
100 Gallons |
UL142 |
SRS-100 |
SRFT-100 |
SRX-100 |
|
UL2080 |
SRS-100 FR |
SRFT-100 FR |
SRX-100 FR |
|
UL2085 |
SRS-100 PT |
SRFT-100 PT |
SRX-100 PT |
|
150 Gallons |
UL142 |
SRS-150 |
SRFT-150 |
SRX-150 |
|
UL2080 |
SRS-150 FR |
SRFT-150 FR |
SRX-150 FR |
|
UL2085 |
SRS-150 PT |
SRFT-150 PT |
SRX-150 PT |
|
200 Gallons |
UL142 |
SRS-200 |
SRFT-200 |
SRX-200 |
|
UL2080 |
SRS-200 FR |
SRFT-200 FR |
SRX-200 FR |
|
UL2085 |
SRS-200 PT |
SRFT-200 PT |
SRX-200 PT |
|
275 Gallons |
UL142 |
SRS-275 |
SRFT-275 |
SRX-275 |
|
UL2080 |
SRS-275 FR |
SRFT-275 FR |
SRX-275 FR |
|
UL2085 |
SRS-275 PT |
SRFT-275 PT |
SRX-275 PT |
|
325 Gallons |
UL142 |
SRS-325 |
SRFT-325 |
SRX-325 |
|
UL2080 |
SRS-325 FR |
SRFT-325 FR |
SRX-325 FR |
|
UL2085 |
SRS-325 PT |
SRFT-325 PT |
SRX-325 PT |
|
400 Gallons |
UL142 |
SRS-400 |
SRFT-400 |
SRX-400 |
|
UL2080 |
SRS-400 FR |
SRFT-400 FR |
SRX-400 FR |
|
UL2085 |
SRS-400 PT |
SRFT-400 PT |
SRX-400 PT |
UL142 Secondary Containment, UL2080
Fire-Rated, UL2085 Fire Protected
Greater than 400 gallons contact Simplex.
The SRM Series Manual
Day Tank provides basic storage only.
It includes a manual fuel fill port and a mechanical level gauge.
The standard SRM package includes a UL142 listed tank. Limited
options are available.
|
|
|
|
Engineers
Specifications
Click here
for a text file of these specifications.
|
Sample specification for UL-142
double-wall secondary containment construction day tank with
on-board supply duplex pumps drawing from a remote main source
tank.
The following defines a day tank with a duplex pump system designed
for delivery of fuel from a source storage tank to a day tank,
approximately 200-feet horizontal and within 18-feet of vertical
lift from the lowest point via a pump set installed on the day
tank. At this site, consideration must be given to suction lift
characteristics of pumps: this system will operate in the suction
lift capability curve of the pumps. Therefore, pipe size of both
supply and return lines is paramount to both reduce friction
in the supply line and allow for free flow return of fuel in
the return line. A foot valve is required in this system if source
tank is below day tank. If source tank is below day tank, manual
priming is required. Once primed, the system remains so from
the foot-valve on the supply line in the main source tank to
the inlet of the day tank mounted supply pumps.
A full flow overflow return pipe from each day tank back to the
bulk source tank must be provided. Working vents to outdoors
must be provided as well as an emergency vent for tanks 100 gallons
and larger. If source tank is located above the level of the
day tank, an overflow return pump and inlet solenoid is required.
See below.
Fuel Oil Day Tank
1.0 General: Provide a packaged design fuel oil day
tank for each prime mover. Day tank shall be complete in all
respects in order to provide the prime mover with a reliable,
local source of fuel. Day tank shall be for use with main tank
and fuel delivery system described above in order to provide
an automatic, self-refilling fuel supply system.
1.1 The day tank shall be designed and supplied
as an engineered system by the manufacturer. Each tank shall
be of packaged design to include all inlet flow control devices,
other valves, level controls, pump control, indicators, alarms
and all other devices as required to form an integrated, functional
system such that field installation is restricted largely to
external piping, wiring and such intermediate devices that are
required by code and/or good engineering practice to interconnect
the bulk source of supply to the day tank, the day tank to the
prime mover and to provide for external vents as per local codes
and UL142, NFPA31 and NFPA37.
1.1.1 The system shall be for use with fuel oil as described
by NFPA321, Basic Classification of Flammable and Combustible
Liquids. As defined by this standard, the fuel supply system
shall be for use with combustible liquids, those
having a flash point at or above 100°F and further defined
as class II or class III liquids. In no case shall a liquid defined
as flammable, or as class I or as having
a flash point less than 100°F be used. In every case, the
system shall not be used or applied at a temperature in excess
of the flash point of the contents. Electrical equipment used
in the system shall be in accordance with NFPA30, section 5-7,
wherein it states For areas where class II or class III
liquids only are stored or handled at a temperature below their
flash points, the electrical equipment may be installed in accordance
with provisions of NFPA70, National Electric Code, for ordinary
locations...
1.1.2 The system shall be designed and installed in accordance
with applicable sections of NFPA30, NFPA31, NFPA37, UL80 and
UL142. The day tank shall bear the label of Underwriters Laboratories
standard 142 and UL508.
1.2 Installation General: The day tank shall be
installed adjacent to the prime mover, on the same grade. Install
(as shown on the plan drawings, [as detailed herein]) on a housekeeping
pad adjacent to the prime mover. Anchor tank to the pad. |
1.2.1
Provide schedule 40, ASTM A 53, black iron pipe connections to
the day tank as shown. Make all connections to fixed installed
pipe with pipe unions to facilitate tank service/removal.
(1) Supply to day tank, inlet to day tank pump
(2) Day tank overflow to bulk supply
(3) Supply and return to prime mover, as recommended by manufacturer.
(4) Vent sizes shall be as shown and as required by local codes
and by UL 142,NFPA31 and NFPA37 as well as project specification
requirements.
1.3 Day tank ratings
1.3.1 Capacity: ( ) gallons
1.3.2 Power requirements: ( )V AC, single-phase, 60Hertz,
15A dedicated branch circuit
1.3.3 Day tank construction
1.3.3.1 All welded steel atmospheric tank of rectangular,
double-wall secondary containment, welded construction built
in accordance with codes and standards noted above for indoor
use with fuel oil
1.3.3.2 Pipe thread connections shall be provided for
fuel oil supply from remote pump set, supply to prime mover,
return from prime mover, overflow to main tank, vents, and drain
with fire rated ball valve. A weatherproof, screened vent cap
shall be provided as a loose item for field installation at the
outdoor vent termination. A weighted type emergency vent cap
shall be supplied installed on the primary tank and secondary
containment emergency vent ports (100 gallon and larger).
1.3.3.3 The tank shall be equipped with a welded steel
channel base suitable for bolt attachment to a concrete pad
1.3.3.4 The tank shall have interior corrosion inhibitor
to deter corrosion prior to installation and use
1.3.3.5 The exterior of the day tank shall receive a heavy-duty
industrial anti-corrosion coating and be finish painted
1.3.3.6 All day tank system components shall be protected
by a removable or hinged steel equipment cover.
1.3.3.7 Day tank shall be factory leak tested at 3PSI.
1.3.3.8 The tank shall be steel double-wall secondary
containment construction bearing the UL 142 label. The containment
shall be equipped with a leak detector that shall activate the
leak alarm described below. A drain with fire rated
ball valve is to be supplied. The containment shall be equipped
with a separate e-vent as required by UL 142.
1.3.3.9 Supply fire rated ball valves as follows:
1. Day tank drain
2. Secondary containment drain
1.4 Fuel delivery system: Provide installed upon
the day tank, a duplex fuel oil pump and duplex pump controller
with automatic alternator for supply of fuel from the main tank
to the day tank. This is a suction-lift application: adequate
pipe sizes must be used in the system and a foot valve must be
installed in the main tank if main is below level of day tank.
Manual priming of the system is required.
1.4.1 Duplex pumps: (Specify GPM, up to 25GPM) at 1725
rpm, when operating with fuel oil having a viscosity of 32SSU.
1.4.2 Direct drive, motor driven pumps coupled via flexible
coupling.
1.4.3 Motors to be TEFC construction, HP as required for
pump at 50 PSI NEMA type B, continuous duty at 40°C, 1725
RPM, 120V AC, 60 hertz, 1.15 service factor
1.4.4 Pumps to be directly driven, positive displacement,
internal gear type with mechanical shaft seal and cast iron body,
machined steel gears.
1.4.5 Fire rated shutoff ball valves on pump inlets
1.4.6 Pump check valve, spring-type, cast iron construction
1.4.7 Flowswitch each pump
1.4.8 Suction strainer, cast iron wye type fuel oil strainer
on each pump suction
1.4.9 Provide a piston type, 0.1 gallon per stroke hand
pump installed and piped and equipped with fire-rated shutoff
valves.
1.4.10 (If source tank is above day tank) Inlet flow control
solenoid valve each pump. Stainless steel construction, with
fire-rated bypass valve.
1.4.11 (If source tank is above day tank) Supply an overflow
return pump at 150% minimum capacity, of supply pump and of identical
construction. Add overflow return pump controller to paragraph
1.5 below. |
1.5
Day tank level controller. A UL Listed, integrated design, digital
level controller shall be supplied which provides differential
level control for activation of pumps, duplex pump alternator,
tank level indication, system alarms and manual operating controls.
Level controller shall be self-contained as a unit within a NEMA4
enclosure integral with the day tank assembly.
1.5.1 PLC based with 6-inch, color, touch-panel operator
interface
1.5.2 Dual level sensor input:
-4-20mA continuous sensor, analog-to-digital input
-Point sensing float switches: low, refill start, refill stop,
high, checkpoint for automatic cross check of sensors
1.5.3 Leak sensor
1.5.4 Spare I/O for options and design-build features
1.5.5 MODBUS and Ethernet network compatible
1.5.6 4-20mA loop output for tank level
1.5.7 Operator touch-panel interface functions:
-HOA switch
-Test
-Reset
-Alarm silence
-Numeric display of tank level in gallons (liters)
-Graphic condition display of tank level and pump/status/alarm
condition
-Message indicators for status and alarm, including:
-Normal operation
-Pump running (fill, return, single or multiple pumps)
-Tank filling
-Loss of flow
-Low
-Critical low
-High
-Critical high
-Leak
-Not in auto
-Controller failure with specific message
-Other messages as determined by design-build option configuration
1.5.8 Relay dry contact outputs for the following (5A,
SPDT):
-Low alarms
-High alarms
-Leak
-Not in auto
-Other alarms as determined by design-build option configuration
1.6 Day tank testing
1.6.1 The day tank shall be supplied with manufacturers
test certificates as below Tank test: pressure test, leak proof
test and structural integrity/appearance test
1.6.1.2 Level controller: operational test of level sensors,
level indicator, level control, alarms, backup devices
1.6.1.3 Pump: vacuum test, flow test, pressure test, leak
proof test, ampere/voltage test, load test, overload test.
1.7 Day tank manual
1.7.1 The day tank shall be supplied with an illustrated
manufacturers manual that includes the following:
1.7.1.1 Registration certificate
1.7.1.2 Glossary
1.7.1.3 Equipment list
1.7.1.4 Detailed description of operation
1.7.1.5 Pump specifications
1.7.1.6 Installation instructions
1.7.1.7 Troubleshooting instructions
1.7.1.8 Maintenance instructions
1.7.1.9 Piping diagram
1.7.1.10 Electrical drawing
1.7.1.11 Exploded view parts drawing/parts list
1.7.1.12 Dimensional drawing
1.7.1.13 Warranty card
1.8 Supply a manufacturers 2-year field service
warranty which covers all parts and all labor for guarantee of
parts and workmanship as specified herein.
1.9 The day tank system, shall be designed and
manufactured by a single supplier and be a standard product in
serial production. The manufacturer shall have at least 10 years
experience in the design and manufacture of these products. This
system shall be a Model SRS Packaged Design Fuel Oil Day Tank
as manufactured by Simplex, Inc., Springfield, Illinois. |