Tank
Filling
Systems
SmartPump

|
SmartPump
|
 |

SPECIFICATIONS
Fitting size: 2", 3" or 4"
Spill containment: 7 gallons
Paint: white
Net weight: 617 lbs. (Oil),
667 lbs. (Gas)
Level transmitter fitting: 2"
SmartPump includes:
Freestanding, pad mountable, open construction pumpset with weatherproof
and lockable fill box with 7 gallon spill containment sump and
weatherproof and lockable control box
2", 3" or 4" fittings
Quick disconnect hose coupling with dust plug
Inlet shutoff valve
Check valve
Outlet shutoff valve
Line purging valve
Spill sump drain valve
High capacity transfer pump, see details below
Automatic controller, described below
Ground stud
Controller includes:
Level transmitter for installation in 2" tank fitting minimum
90% and 95% visual alarms
Tank leak alarm
Audible alarm horn activated by alarms above
Power available indicator
Control power on-off switch
Pump start/stop pushbuttons
Top-off/hose drain mode pushbutton
Pump starter
TYPE 3R control enclosure (fuel oil version)
Explosion proof control enclosure (gasoline version)
Sales Bulletin
Options
List, Couplers and Adapters
|
|
The Simplex SmartPump is
a tank fill pump with intelligence. The SmartPump is a factory
packaged system for transfer of fuel from gravity trucks to storage
tanks and control of filling operations to prevent overfill and
allow for full draining of the truck delivery hose. The SmartPump
provides a ready means of ground level connection of the fill
hose, and captures spills that may occur at the fill point during
filling operations. The SmartPump includes a high capacity fuel
transfer pump and intelligent pump controls. The unique design
and intelligence of the SmartPump allows full and easy draining
of the truck fill hose prior to disconnect. The SmartPump detects
the Tank Full level, stops filling operations and activates an
alarm. The SmartPump allows the operator to continue filling
and/or drain the fill hose up to the High Fuel level at which
time all filling operations are locked out and an alarm is activated.
A leak detection circuit prevents filling of leaking tanks. Visual
and audible level and leak alarms are provided.
The Simplex SmartPump is available for use with fuel oil (Class-II
liquids) or gasoline (Class-I liquids).
Single or multiple tank controllers are available. Multiple
Tank SmartPumps allow operator selection of the tank
to be filled with automatic lockout of all other tanks.
|
PUMP
PERFORMANCE |
|
HEAD |
GPM |
SmartPump
with 5 HP pump
3" or 4" inlet: |
75 ft.
65 ft.
55 ft.
40 ft.
25 ft. |
200
250
300
350
400 |
SmartPump
with 2 HP pump
2" inlet: |
55 ft.
45 ft.
35 ft.
15 ft. |
75
125
150
200 |
 |
How it works:
|
1. |
Delivery truck arrives and driver
proceeds to SmartPump to make fuel delivery. |
|
2. |
Connect ground cable. |
|
3. |
Unlock fill box and control box. |
|
4. |
Turn on controller. |
|
5. |
Connect delivery hose to hose coupling. |
|
6. |
Open valve on truck. |
|
7. |
Open SmartPump inlet valve. |
|
8. |
Open SmartPump outlet valve. |
|
9. |
Start SmartPump. |
|
10. |
Fuel is delivered to tank. |
|
11. |
At 90% level, audible and visual
alarm activates and alerts driver, SmartPump stops. |
|
12. |
Driver may stop delivery at this
point. |
|
13. |
Driver can restart SmartPump by
pressing override pushbutton and pressing Pump
Start pushbutton. Pump will run for 30 second intervals. |
|
14. |
Driver can continue filling or
drain delivery hose at this time. |
|
15. |
To drain hose, driver closes truck
valve and breaks hose connection at tank and allows SmartPump
to empty hose. |
|
16. |
Driver may restart SmartPump in
30 second intervals, but all filling and hose draining operations
must be ended and truck valve closed prior to reaching 95% level. |
|
17. |
At 95% level, audible and visual
alarm activates and SmartPump stops. SmartPump can not be restarted. |
|
18. |
Close SmartPump outlet valve. |
|
19. |
Close SmartPump inlet valve. |
|
20. |
Disconnect delivery hose and ground
cable. |
|
21. |
Turn controller off. |
|
22. |
Close and lock SmartPump doors. |
|
23. |
Proceed to next delivery, where,
hopefully, the owner has had the foresight to install a Simplex
SmartPump. |
|
|
|
 |

Two-Tank SmartPump
with Optional Full Enclosure |
|
|
Options |
|
|
|
|
Inlet fittings:
Standard quick disconnect coupling:
2", 3" or 4":
- 2" available for 2 hp SmartPump
- 3" and 4" available for 5 hp SmartPump
Dry connect adaptor: 2" or 3":
- 2" available for 2 hp SmartPump
- 3" available for 5 hp SmartPump
Valves:
Fusible link fire valve, installed on outlet
Fire rated shutoff valves, in lieu of standard bronze valves
Fire rated shutoff valve assembly for installation on aboveground
storage tank fuel inlet, including fire rated ball valve and
self-closing fusible link valve (shipped loose) |
Leak sensors:
Tank leak sensor, float switch type, for mounting in a vertical
position in collection sumps, monitoring pipes and steel double
wall tank sumps. For installation in 2" fitting. SmartPump
controller includes: tank leak alarm, tank fill shutoff, alarm
contacts.
Tank leak sensor, as above, except optical type, for restricted
space installation in tank annular space, double wall pipe collection
sump, etc. |
Level indicator gauges:
Digital level indicator, percent level reading. Includes level
transmitter for installation in 2" NPT fitting
Digital tank monitor with display of tank level in gallons, liters
or percent; high and low level alarms, audible alarm; output
contact. Includes level transmitter for installation in 2"
NPT fitting
Hydrostatic level gauge, hand pump type with 5" dial type
indicator calibrated in gallons. Transmitter installed in 2"
tank fitting
Click here to see
the complete list of options. |