SIMPLEX DAY
TANK CONTROL DEVICES AND ALARMS OPTIONS
SDE = Economy
Day Tank, SST = Super Day Tank, SMT = Manual Day Tank
A = Available, NA = Not Available, S = Standard
Other Day
Tank Options:
Mechanical, Containment/Rupture
Basins, Duplex Pump Systems,
Gravity Fed,
Sight Glasses, Level Indicators and
Gauges, Pumps and Motors
|
|
NO. |
SDE |
SST |
SMT |
DESCRIPTION |
|
260 |
NA |
A |
NA |
Disconnect switch with
door interlock for main power inlet connection. Guarded terminals
for line connections, pad lockable handle mechanism interlocked
to prevent opening of door until switch is turned off. |
|
261 |
A |
A |
NA |
On-Off day
tank system circuit breaker with short circuit trips. Mounted
on day tank.
a) For use with standard and optional single phase, AC motors;
DC motors
b) For use with optional 3-phase, AC motors |
|
262 |
A |
A |
NA |
50VA, 480/240: 120, single
phase, control power transformer |
|
265 |
NA |
A |
A |
Day tank heater, 120V,
immersion type, thermostatically controlled. Includes low level
cutout. |
|
270 |
A |
S |
NA |
Power available green
pilot light |
|
280 |
A |
S |
NA |
Pump Run-Off-Automatic
operation mode selector switch |
|
285 |
NA |
A |
NA |
Loss of flow alarm. Sensor
detects fuel flow from pump and activates alarm if flow is lost
while pump is running. Adjustable sensitivity and time delay.
(For option 345: Duplex Systems, order two.) |
|
295 |
A |
S |
A |
Remote low fuel level
alarm dry signal contacts. Provided by separate float switch
sensing at 25% of day tank fuel capacity. For use in activation
of solid-state annunciator circuits, lamps, small relays. 20VA
to 50V DC/240V AC |
|
297 |
A |
S |
A |
Remote high fuel level
alarm dry signal contacts. Provided by separate float switch
sensing at 95% of day tank fuel capacity. For use in activation
of solid-state annunciator circuits, lamps, small relays. 20VA
to 50V DC/240V AC |
|
299 |
A |
S |
NA |
Auxiliary relay for use
with options 295 and 297 above. Used to interface float switch
signal to high current device. 3 PDT, 10A, 240V AC. Specify coil
voltage |
|
311 |
NA |
A |
NA |
Local/remote low fuel
level alarm. Consists of red alarm light on day tank control
panel plus dry signal contacts for remote alarm. Activated by
separate float switch sensing 25% of day tank fuel capacity.
Dry contacts are 3 PDT rated 10A, 30V DC/240V AC. Specify coil
voltage. |
|
312 |
NA |
S |
NA |
Local/remote high fuel
level alarm. Consists of red alarm light on day tank control
panel plus dry signal contacts for remote alarm. Activated by
separate float switch sensing 95% of day tank fuel capacity.
Dry contacts are 3 PDT rated 10A, 30V DC/240V AC. Specify coil
voltage. |
|
325 |
NA |
S |
NA |
High fuel level emergency
pump-stop switch with local and remote alarm. |
|
326 |
A |
NA |
NA |
High level cutout for
SDE Series only. Float switch to disable pump control contactor
. |
|
329 |
NA |
A |
NA |
Low fuel level red light
to indicate low fuel in the remote main storage tank. Consists
of panel mounted light and terminal block only. Others to supply
signal. Specify voltage. |
|
333 |
NA |
A |
NA |
Critical low fuel level
alarm-engine shut down. To prevent loss of engine fuel prime
from air ingestion due to loss of day tank fuel level. When day
tank fuel level reaches imminent failure point, (approximately
1 above engine suction point) separate float switch in
day tank closes, providing signal to engine for shutdown, signal
for remote annunciator, activation of alarm light on day tank
control panel. |
|
334 |
NA |
A |
NA |
Alarm horn installed
on day tank |
|
340 |
A |
S |
NA |
Pump Running
amber light |