Conversion Factors
Hydraulic Formulas
Head
and Pressure Equivalents
Pressure
and Conversion Table
Motors for Pump Drive Continuous Duty: Single
Phase, Three Phase, DC |
Conversion Factors
1HP = 33,000 ft. lbs.
per minute
1HP = 42.4 btu per minute
1HP = 0.746 kwhr (kilowatt hours)
1 U.S. Gallon = 231 cubic inches
Pipe Volume varies as the square
of the diameter -
Volume in Gallons = 0.0034 x D² x L
D = inside diameter of pipe in inches, L = length in inches
Velocity in Feet Per Second = ( 0.408 x flow (gpm) ) ÷ D²
D = inside diameter of pipe in inches
Atmospheric Pressure at Sea
Level = 14.7PSI
Atmospheric pressure decreases approximately 0.41PSI for each
one thousand feet of elevation up to 23,000 feet.
Pressure (PSI) = feet head x 0.433 x specific gravity
Specific Gravity of Oil = 0.85 approximately
Thermal Expansion of Oil = approximately 1 cubic inch per 1
gallon per 10°F rise in temperature
Hydraulic
Formulas
Horsepower = ( GPM x PSI ) ÷ 1714
Torque (lb. in.) = ( CU IN./REV. x PSI ) ÷ 2
Torque (lb. in.) = ( HP X 63025 ) ÷ RPM
Flow (gpm) = ( CU IN./REV x RPM ) ÷ 231
Head
and Pressure Equivalents
The specific gravity of the liquid must be considered when converting
pressure from feet of water to P.S.I. Here are some typical conversion
figures:
1 P.S.I. = 2.30 feet of water (specific gravity 1.0)
1 P.S.I. = 2.88 feet of oil (specific gravity 0.8) |
Conversion
Factors
Hydraulic
Formulas
Head
and Pressure Equivalents
Pressure
and Conversion Table
Motors for Pump Drive Continuous Duty: Single Phase, Three
Phase, DC |
SINGLE PHASE MOTORS
FOR PUMP DRIVE
CONTINUOUS DUTY, 40°C, UL RECOGNIZED
Single Phase: Split
Phase Start, Drip Proof, Rigid Base, Class B Insulation,
Moderate Starting Torque, Sleeve Bearing
|
HP |
RPM |
VOLTAGE |
NEMA
FRAME |
THERMAL
PROF. |
SERVICE
FACTOR |
APPROX.
F.L. AMPS |
|
1/3 |
1800 |
115 |
48 |
AUTO |
1.0 |
6.6 |
|
1/2 |
1800 |
115 |
56 |
NONE |
1.0 |
9.2 |
Single Phase: Capacitor
Start, Drip Proof, Rigid Base, Class B Insulation,
Moderate Starting Torque, Sleeve Bearing
|
HP |
RPM |
VOLTAGE |
NEMA
FRAME |
THERMAL
PROF. |
SERVICE
FACTOR |
APPROX.
F.L. AMPS |
|
1/3 |
1800 |
115/230 |
48 |
AUTO |
1.0 |
7.0/3.5 |
|
1/2 |
1800 |
115/230 |
56 |
AUTO |
1.0 |
9.2/4.6 |
|
3/4 |
1800 |
115/230 |
56 |
AUTO |
1.0 |
10.4/5.2 |
Single Phase: Capacitor
Start, Drip Proof, Rigid Base, Class B Insulation,
High Starting Torque, Ball Bearing
|
HP |
RPM |
VOLTAGE |
NEMA
FRAME |
THERMAL
PROF. |
SERVICE
FACTOR |
APPROX.
F.L. AMPS |
|
1 |
1800 |
115/208-230 |
56 |
AUTO |
1.15 |
13.4/6.8-6.7 |
|
1/2 |
1800 |
115/208-230 |
56H |
AUTO |
1.15 |
18.0/9.3-9.0 |
|
2 |
1800 |
115/208-230 |
145T |
NONE |
1.15 |
21.0/11.3-10.5 |
|
3 |
1800 |
115/208-230 |
184T |
NONE |
1.15 |
33.0/16.5 |
|
5 |
1800 |
208-230 |
184T |
NONE |
1.15 |
23.0-21.0 |
|
7 1/2 |
1800 |
208-230 |
215T |
NONE |
1.15 |
35.2 |
Single Phase: Capacitor
Start, Totally Enclosed, Fan-Cooled, Rigid Base,
Class B Insulation, NEMA-L ( greater or = 1.0 HP ) High Starting
Torque, Ball Bearing
|
HP |
RPM |
VOLTAGE |
NEMA
FRAME |
THERMAL
PROF. |
SERVICE
FACTOR |
APPROX.
F.L. AMPS |
|
1/3 |
1800 |
115/208-230 |
56 |
AUTO |
1.15 |
6.6/3.1-3.3 |
|
1/2 |
1800 |
115/208-230 |
56 |
AUTO |
1.15 |
8.8/4.2-4.4 |
|
3/4 |
1800 |
115/208-230 |
56 |
AUTO |
1.15 |
11.0/5.4-5.5 |
|
1 |
1800 |
115/208-230 |
56 |
AUTO |
1.15 |
13.4/6.8-6.7 |
|
1 1/2 |
1800 |
115/208-230 |
56H |
AUTO |
1.15 |
15.2/8.2-7.6 |
|
2 |
1800 |
115/208-230 |
145T |
NONE |
1.15 |
18.8/9.4 |
|
3 |
1800 |
115/208-230 |
184T |
NONE |
1.0 |
34.0/17.0 |
|
5 |
1800 |
208-230 |
213T |
NONE |
1.0 |
27.5-26.0 |
|
7 1/2 |
1800 |
208-230 |
215T |
NONE |
1.0 |
36.5-33.0 |
|
Conversion
Factors
Hydraulic
Formulas
Head
and Pressure Equivalents
Pressure
and Conversion Table
Motors for Pump Drive Continuous Duty: Single
Phase, Three Phase, DC |
THREE PHASE MOTORS
FOR PUMP DRIVE
CONTINUOUS DUTY, 40°C, UL RECOGNIZED
Three Phase: Drip
Proof, Rigid Base, Class B Insulation, NEMA B,
High Starting Torque, Ball Bearing
|
HP |
RPM |
VOLTAGE |
NEMA
FRAME |
THERMAL
PROF. |
SERVICE
FACTOR |
APPROX.
F.L. AMPS |
|
1/3 |
1800 |
208-230/460 |
56 |
AUTO |
1.35 |
1.5-1.6/0.8 |
|
1/2 |
1800 |
208-230/460 |
56 |
AUTO |
1.35 |
2.3-2.4/1.2 |
|
3/4 |
1800 |
208-230/460 |
56 |
AUTO |
1.25 |
2.9-3.0/1.5 |
|
1 |
1800 |
208-230/460 |
56 |
AUTO |
1.15 |
3.5-3.6/1.8 |
|
1 1/2 |
1800 |
208-230/460 |
145T |
AUTO |
1.15 |
4.8-4.8/2.4 |
|
2 |
1800 |
208-230/460 |
145T |
AUTO |
1.15 |
6.2-6.2/3.1 |
|
3 |
1800 |
208-230/460 |
145T |
AUTO |
1.15 |
9.2-8.6/4.3 |
|
5 |
1800 |
230/460 |
184T |
AUTO |
1.15 |
13.2/6.6 |
|
7 1/2 |
1800 |
230/460 |
213T |
AUTO |
1.15 |
20.0/10.0 |
|
10 |
1800 |
230/460 |
215T |
AUTO |
1.15 |
26.6/13.3 |
Three Phase: Totally
Enclosed, Fan-Cooled, Rigid Base, Class B Insulation,
Class F (182T-254T), NEMA B, High Starting Torque
|
HP |
RPM |
VOLTAGE |
NEMA
FRAME |
APPROX.
F.L. AMPS |
|
1/3 |
1800 |
208-230/460 |
56 |
1.5-1.6/0.8 |
|
1/2 |
1800 |
208-230/460 |
56 |
2.3-2.4/1.2 |
|
3/4 |
1800 |
208-230/460 |
56 |
2.9-3.0/1.5 |
|
1 |
1800 |
208-230/460 |
56 |
3.5-3.6/1.8 |
|
1 1/2 |
1800 |
208-230/460 |
145T |
4.8-4.8/2.4 |
|
2 |
1800 |
208-230/460 |
145T |
6.0-5.8/2.9 |
|
3 |
1800 |
208-230/460 |
145T |
8.6/4.3 |
|
5 |
1800 |
230/460 |
184T |
14.0-13.2/6.6 |
|
7 1/2 |
1800 |
230/460 |
213T |
21.0-20.0/10.0 |
|
10 |
1800 |
230/460 |
215T |
28.0-27.0/13.5 |
|
Conversion
Factors
Hydraulic
Formulas
Head
and Pressure Equivalents
Pressure
and Conversion Table
Motors for Pump Drive Continuous Duty: Single
Phase, Three Phase, DC |
DC MOTORS - AMPERE RATINGS AND
FUSE SIZES
FOR PUMP DRIVE
CONTINUOUS DUTY, 40°C, UL RECOGNIZED
|
HP |
RATINGS
OF DC MOTORS
FULL-LOAD AMPERES |
AMP.
CAP. OF FUSES FOR MOTORS
RECOMMENDED VALUES |
|
120 VOLTS |
240 VOLTS |
120 VOLTS |
240 VOLTS |
|
1/8 |
1.4 |
.7 |
3 |
3 |
|
1/6 |
1.8 |
.9 |
3 |
3 |
|
1/4 |
2.9 |
1.5 |
5 |
3 |
|
1/3 |
3.6 |
1.8 |
5 |
3 |
|
1/2 |
5.2 |
2.6 |
7 |
3 |
|
3/4 |
7.4 |
3.7 |
10 |
5 |
|
1 |
9.4 |
4.7 |
15 |
7 |
|
1 1/2 |
13.2 |
6.6 |
20 |
10 |
|
2 |
17 |
8.5 |
25 |
12 |
|
3 |
25 |
12.2 |
30 |
15 |
|
5 |
40 |
20 |
50 |
25 |
|
7 1/2 |
58 |
29 |
80 |
40 |
|
10 |
76 |
38 |
100 |
50 |
|