SIMPLEX PACKAGED PUMP SETS (SPS/SKS SERIES)
DUPLEX PUMP SYSTEMS OPTIONS

Other options:
Mechanical, Control Devices and Alarms, Level Controllers, Gauges, and Fill Controllers, and Pumps and Motors
 

Duplex pump options are used to increase the reliability of a pumping system through the addition of a second, backup pump and level control. In a duplex system, one pump is designated the “lead” pump and the other is the “lag” pump. The lead pump automatically refills the tank over the tank’s normal operating range of 50% to full. Normally, once the tank has been initially filled, the fuel level should never drop below 50%. Less than 50% is indicative of either a failure of the lead pump or consumption in excess of pump capacity. The lag pump and its separate level controller, acting as a backup senses a drop in fuel level below 50% and starts the lag pump, which then continues to run, along with the lead pump, until the tank is full.

When ordering, remember that duplex systems include two motor-pumps and therefore require a quantity of two of any option related to the motor or pump, such as valves, strainers, etc.

NO.

DESCRIPTION

345
Multifunction duplex pump controller system providing selectable operating modes, including:

1) Automatic lead pump alternating with automatic lag pump backup
2) Manual lead pump selection, automatic alternating, automatic lag pump backup
3) Automatic twin pump operation (both pumps run simultaneously) automatic level control backup
4) Manual operation

Basic System includes the following:

1) Mode selector switch
2) Pump running indicators for each pump
3) Two 1/3HP, 120V, 2GPM pumps, with check valves

285
Sensor to detect pump flow and indicate failure of pump. Use with duplex pump controller to start lag pump and activate alarm. (Order two for option 345: Duplex Pump Systems.)

346
Running time meter, one for each pump. (Order two for option 345: Duplex Pump Systems.)

347
Manual duplex pump selector switch. Used to select one of two pumps or both pumps for automatic operation. In single pump mode, off-line pump not available for automatic operation. Includes:

1) Selector switch with positions “pump-1,” “pump-2,” “both”
2) Pump running lights
3) Two 1/3 HP, 120 V, 2 GPM pumps, with check valves


SIMPLEX PACKAGED PUMP SETS (SPS/SKS SERIES)
PUMPS AND MOTORS OPTIONS

Other options:
Mechanical, Control Devices and Alarms, Level Controllers, Gauges, and Fill Controllers, and Duplex Pump Systems


Note: The following optional pumps and motors are in lieu of basic unit.
The 2 GPM Super-XL pump and the 1/3 HP, 230V AC, single-phase, 60 Hertz motor
are the standard pump and motor provided with the basic unit.
Pump capacity at 1725 RPM. 50 Hz operation reduces capacity to 83%.
 

NO.
Super-XL Pumps
High-tech hydraulic pump featuring pressure-loaded, self-compensating gears and a mechanical shaft seal designed for applications where the pump starts and stops on demand. For more information click here.

400
7 GPM pump in lieu of 2 GPM basic unit pump. Requires a ½ HP motor not included in price. (¾” NPT)

410
10 GPM pump in lieu of 2 GPM basic unit pump. Requires a ¾ HP motor not included in price. (¾” NPT)

415
17 GPM pump in lieu of 2 GPM basic unit pump. Requires a 1 HP motor not included in price. (¾” NPT)

417
25 GPM pump in lieu of 2 GPM basic unit pump. Requires a 1½ HP motor not included in price. (1¼” NPT)

NO.
420 Series Pumps
High performance cast iron/steel rotor pump for use with heavy fuel or continuous circulation systems where pump runs virtually nonstop. HP is minimum motor size. For more information click here.

420
3 GPM, ½ HP

422
5 GPM, ¾ HP

424
11 GPM, 1 HP

426
13 GPM, 1½ HP

428
28 GPM, 3 HP

430
45 GPM, 5 HP

432
61 GPM, 7½ HP

NO.
Transformers and Motors
3-phase motors may be operated at 190/380V, 50Hz. 50Hz operation reduces pump capacity to 5/6.

510
Transformer, 480/120V AC, single phase, 50-60 Hertz for use with standard and optional 1/3 HP motors

511
Transformer, 480/120V AC, single phase, 50-60 Hertz for use with optional ½ HP motors

605
1/3 HP, 230V AC, single phase, 60 Hertz motor, ODP

615
1/3 HP, 110V AC, single phase, 50 Hertz motor, ODP

616
1/3 HP, 220V AC, single phase, 50 Hertz motor, ODP

621
1/3 HP, 230/460V AC, 3-phase, ODP motor with starter. Specify voltage.

622
1/3 HP, 230/460V AC, 3-phase, TEFC motor with starter. Specify voltage.

630
1/3 HP, 12V DC motor

635
1/3 HP, 24V DC motor

645
1/3 HP, 115V AC, single phase, 60 Hertz motor, TEFC

700
½ HP, 115V AC, single phase, 60 Hertz motor, ODP

705
½ HP, 230V AC, single phase, 60 Hertz motor, ODP

715
½ HP, 110V AC, single phase, 50 Hertz motor, ODP

716
½ HP, 220V AC, single phase, 50 Hertz motor, ODP

721
½ HP, 230/460V AC, 3-phase, ODP motor with starter. Specify voltage.

722
½ HP, 230/460V AC, 3-phase, TEFC motor with starter. Specify voltage.

730
½ HP, 12V DC motor

735
½ HP, 24V DC motor

745
½ HP, 115V AC, single phase, 60 Hertz motor, TEFC

768
Single phase magnetic motor starter with overload relay and control transformer. Includes disconnect switch with short circuit protection. For 115V AC or 230V AC, single phase, motors.

770
3-phase magnetic motor starter with overload relay and control transformer. Includes disconnect switch with short circuit protection. For 230V AC or 460V AC, 3-phase, motors.

800
¾ HP, 115V AC, 60 Hertz, single phase motor, ODP

805
¾ HP, 230V AC, 60 Hertz, single phase motor, ODP

822
¾ HP, 230/460V AC, 60 Hertz, 3-phase motor, TEFC, with motor starter. Specify voltage.

825
¾ HP, 230/460V AC, 60 Hertz, 3-phase motor, with motor starter, ODP. Specify voltage.

845
¾ HP, 115/230V AC, 60 Hertz, single phase motor, TEFC. Specify voltage.

900
1 HP, 115V AC, 60 Hertz, single phase motor, ODP

905 
1 HP, 230V AC, 60 Hertz, single phase motor, ODP

922
1 HP, 230/460V AC, 60 Hertz, 3-phase motor, TEFC, with motor starter. Specify voltage.

925
1 HP, 230/460V AC, 60 Hertz, 3-phase motor, with motor starter, ODP. Specify voltage.

945
1 HP, 115/230V AC, 60 Hertz, single phase motor, TEFC. Specify voltage.

1000
1½ HP, 115V AC, 60 Hertz, single phase motor, ODP

1005
1½ HP, 230V AC, 60 Hertz, single phase motor, ODP

1022
1½ HP, 230/460V AC, 3-phase, 60 Hertz, TEFC, with motor starter. Specify voltage.

1025
1½ HP, 230/460V AC, 3-phase, 60 Hertz, with motor starter, ODP. Specify voltage.

1045
1½ HP, 115/230V AC, single phase, 60 Hertz, TEFC. Specify voltage.

1100
2 HP, 115V AC, 60 Hertz, single phase motor, ODP

1105
2 HP, 230V AC, 60 Hertz, single phase motor, ODP

1122
2HP, 208V AC, 3-phase, 60 Hertz motor, ODP

1125
2 HP, 230/460V AC, 60 Hertz, 3-phase motor with motor starter, ODP. Specify voltage.

1145
2 HP, 115/230V AC, 60 Hertz, single phase motor, TEFC. Specify voltage.

1200
3 HP, 115V AC, 60 Hertz, single phase motor, ODP

1205
3 HP, 230V AC, 60 Hertz, single phase motor, ODP

1225
3 HP, 230/460V AC, 60 Hertz, 3-phase motor with motor starter, ODP. Specify voltage.

1305
5 HP, 230V AC, 60 Hertz, single phase motor, ODP

1322
5HP, 230V AC, 3-phase, 60 Hertz motor, TEFC

1325
5 HP, 230/460V AC, 60 Hertz, 3-phase motor with motor starter, ODP. Specify voltage.

1405
7½ HP, 230V AC, 60 Hertz, single phase motor, ODP

1422
7½HP, 208V AC, 3-phase, 60 Hertz motor, ODP

1425
7½ HP, 230/460V AC, 60 Hertz, 3-phase motor with motor starter, ODP. Specify voltage.

Back to Packaged Pump Sets (SPS) Page.
Back to Packaged Pump Sets (SPS) Application Guide Page.
Back to SPS-10 and SPS-20 Dimensions and Key Features Drawings Page.
Back to SPS-30 and SPS-50 Dimensions and Key Features Drawings Page.

Back to top of page.


Back to Options Page 1.
Mechanical, Control Devices and Alarms, Level Controllers, Gauges, and Fill Controllers

Request Quote.
 

Back to Fuel Supply Main Page
 

Simplex, Inc., 1139 North MacArthur Boulevard, Springfield, IL 62702-2314