Large
Portable
dynaMITE
310KW
290KW
217KW
208KW

|
dynaMITE 300
Portable Load Bank
The Simplex dynaMITE 300
Portable Load Bank provides highly versatile load-test capability
for the manufacturers, distributors and users of small-to-medium
size AC power systems to 300KW nominal.
The dynaMITE 300 is suitable for production line, service
shop or field testing of engine generators, UPS systems, ground
power units, auxiliary power units, static inverters or virtually
any other AC power source. This load bank can be applied to all
common AC voltages to 480V maximum, 50-60-400Hz, single or 3-phase.
The dynaMITE 300 is a fully self-contained test instrument
which includes test instrumentation, connection cables, high
capacity cooling system, rugged load elements, complete load
application control devices, and automatic system protection
devices.
The dynaMITE 300 is compact and fully portable and includes
lifting eyes, forklift channels, and moving handles. Connection
cables are conveniently stowed in a cable compartment behind
a hinged door. All instruments and controls are protected by
hinged panel covers.

|

Features
Portable, compact, self-contained
Broad voltage capability
Fine load step resolution
Utilizes the UL Recognized Powr-Web load element
Branch circuit fuse protection of load elements
Toggle switch control of load steps
Complete test instrumentation and system fault protection
Fused control power circuits
Fan motor circuit breaker
Connection cables included
Fast set-up, quick turnaround
Field use capable
|
SPECIFICATIONS
Capacity
315KW at 480V,
3-ph.
290KW at 240V, 3-ph.
217KW at 208V, 3-ph.
208KW at 240V, 1-ph.
Voltage
Operator
selectable:
High: 250-480V AC, 3-ph.
Low: 12-240V AC, 1-ph. or 3-ph.
Frequency
50, 60, 400
Hertz
Load Step Resolution
1KW
Fan/Control Power
User selectable:
External
120V AC, 1-ph., 60Hz, 20A
Internal
240V AC, 1-ph., 60Hz, 3W
240V AC, 3-ph., 60Hz, 4W
120V AC, 1-ph., 60Hz, 2W
Optional Internal, above plus:
480V AC, 3-ph., 50, 60Hz
Airflow
8,000 CFM
Temperature Rating
120°F
max. intake
275°F max. exhaust
Duty Cycle
Continuous
Net Weight
800 lbs.
Dimensions
32 W
x 48 H x 60 D
Enclosure
NEMA-1 drip
proof
Options
KW meter
Running time meter
1% accuracy digital panel meters
Digital power meter
Extended terminal power capability (to 480V, 3-ph., 60Hz)
400Hz instruments
Remote control provision
Companion Load Bank
Vinyl cover
Weatherproof enclosure
Highway trailer
Click here for a complete
list of options available for Large Portable Load Banks.
Sales
Bulletin
Dimensions
and
Key Features Diagram
|
|
|
|
AC Meters, 3½,
+/- 2%
Voltmeter, 0-600V, 50-60Hz
Ammeter, 0-250/1000A
Combination Volt-ammeter Switch
Frequency Meter, Direct Reading (Dial)
Type 45-65 Hz
Voltage Selector Switch
(12-240V/250-480V)
Fan/Control Power Switch
Load Control Switches
Master Load Application Switch
Load Step Switches
|
Normal Operation
Neon Indicator Light
Internal Fan/Control Power Available Neon Indicator
Light
Failure Detection System, Neon Alarm Lights and Lockout
Fan Failure
High Intake Temperature
High Exhaust Temperature
Overvoltage
|
|
Simplex Load Banks can
be used to satisfy the requirements of the National Fire Protection
Association (NFPA) for emergency stand-by power systems. |
|
|
|
Powr-Web Load
Element

Simplex Load Banks utilize the
UL Recognized, Powr-Web load element. The Powr-Web
is an advanced design, air-cooled power resistor specifically
designed for application to load bank systems. The Powr-Web
is conservatively operated at half the maximum temperature rating
of the alloy and features a short-circuit-safe design based on
continuous mechanical support of the resistor by high temperature,
ceramic clad stainless steel rods. The Power Webs
are assembled into discrete trays which are assembled in a vertical
stack. Each tray in the stack is independently
serviceable without disturbing adjacent trays.
 |
Ratings
3333W at 120V
4170W at 139V
8333 watt 240/480V
16,777 watt at 480V
Specifications
Alloy: FeCrAl
Max. continuous temp. rating: 1920°F
Maximum operating temperature as applied in Load Bank: 1080°
F
Cool down time from operating to ambient temperature: 10 seconds
Construction
Calibrated to specific
ohm value
Welded lugs on each end
All load elements are continuously supported by vibration resistant,
ceramic clad, stainless steel throughrods
|
Branch Circuit Fuse Protection
The load of a Resistive Load
Bank consists of a dense array of open, uninsulated power resistors
mounted within a cooling air stream. Since the elements are electrically
live, it is possible for a foreign object to penetrate the element
array and create a short circuit of adjacent elements or a short
to ground. Since the elements are densely packed, it is possible
for a short circuit, once started, to rapidly propagate through
the entire element array. As a Load Bank represents a relatively
large amount of power concentrated within a relatively small
volume, a self-propagating, cascading short circuit would have
catastrophic results.
Simplex virtually eliminates
the dangers of short circuit through the use of branch circuit
fuse protection of the load elements. Per NEC 110-10, protective
devices shall clear a fault without extensive damage
to the circuit components. A Simplex Load Bank is divided into
branch circuits of not more than 50 KW each.
|
|
|
DYNAMITE
300 PORTABLE LOAD BANK
CAPACITY DETAIL
|
|
Voltage (AC) |
480V, 3-PH. |
416V, 3-PH. |
380V, 3-PH. |
240V, 3-PH. |
208V, 3-PH. |
240V, 1-PH. |
|
KW (1.0 P.F.) |
315 |
238 |
197 |
289 |
217 |
208 |
DYNAMITE
300 PORTABLE LOAD BANK
LOAD STEP DETAIL
|
|
KW
EACH STEP (1.0 P.F) |
|
QUANTITY |
480V,
3-PH. |
416V,
3-PH. |
480V,
3-PH. |
240V,
3-PH. |
208V,
3-PH. |
240V,
1-PH. |
|
1 |
- |
- |
- |
1.25 |
.94 |
.84 |
|
1 |
- |
- |
- |
2.5 |
1.9 |
1.7 |
|
1 |
5 |
3.75 |
3.1 |
5 |
3.75 |
3.4 |
|
1 |
10 |
7.5 |
6.3 |
10 |
7.5 |
6.7 |
|
1 |
20 |
15 |
12.6 |
20 |
15 |
13 |
|
3 |
40 |
30 |
25 |
40 |
30 |
26 |
|
2 |
80 |
60 |
50 |
80 |
60 |
52 |
|