Large
Portable
Electra
660KW
560KW
460KW

|
Electra
Portable Load Bank
The Simplex Electra is
a very large capacity, high performance Portable Load Bank designed
to provide the manufacturers, distributors and users of large
AC generators and UPS systems with sophisticated testing capability.
The Electra provides 460KW, 560KW or 660 of resistive
load at both 240V and 480V, 3-phase. It can be applied at any
AC voltage to 480V AC, 50-60-400 Hertz, single or 3-phase. Load
step resolution is 5KW.
The Electra is a totally self-contained testing system.
It includes all resistive load elements, load control devices,
load element circuit protective devices, connection cable set,
cooling system, malfunction detection system, control power supply
and test instrumentation.
Principal Sub-Systems
Load Elements: Simplex Powr-Web chromium
alloy, open wire, continuously supported, power resistor.
Load Control: 3-Pole magnetic contactors.
Load Element Circuit Protection: Branch circuit fuses.
One set of fuses each 50KW branch. Fuses are current limiting
type, 200,000 AIC, 600V, enabling safe use on large generating
or UPS system.
Cooling System: 3-phase, direct-drive fan, 12,500 CFM.
Malfunction Detection System: Protection against fan failure,
high exhaust air temperature, high intake air temperature, overvoltage
and fan reversal.
Control Power Supply: Dual voltage control power transformer
with supply power switchable to internal (generator) or external.
Test Instrumentation: 3½, +/- 2% accuracy
panel meters. Options available.
Remote Control: Load control switch panel removable for
remote operation. Connection plugs will accept optional remote
control cables.
Connection: 12 connection cable set including 3-phase
power cables, ground cable and external control power cord, stored
behind hinged door in rear compartment.
Control Panel
AC instrumentation,
3½, +/- 2% accuracy panel meters:
AC voltmeter with 3-ph. transfer switch
AC ammeter with 3-ph. transfer switch
Frequency meter
Load step control toggle switches
Master load control toggle switch
Control power switch
Voltage selector switch
Fan reversal switch
Operational indicator lights:
Normal Operation
Overvoltage
Fan failure/over temperature
|

Features
High capacity, dual voltage
Fine load step resolution
Toggle switch load control
Utilizes the proven Simplex Powr-Web load element
Branch circuit fuse protection of load elements
Totally self-contained
Fan/control power-source is operator selectable:
Internal Power: Fan and control circuits powered internally,
does not require external power
External Power: Fan and control circuits powered from
external 3-phase outlet or other external source
Integral high capacity cooling fan
3-phase connection cable set stowed in cable compartment
Compact, rugged, portable enclosure
Double wall construction for cool exterior
Control compartments thermally insulated from load elements
Hinge-open control panel doors
Comprehensive automatic malfunction detection system with alarm
lights
Test instrumentation
Remote control capability
|
Simplex Load Banks can
be used to satisfy the requirements of the National Fire Protection
Association (NFPA) for emergency stand-by power systems. |
 |
SPECIFICATIONS
Capacity
Electra
460
460 KW at 240/480V, 3-ph.
345 KW at 208/416V, 3-ph.
307 KW at 240V, 1-ph.
Electra-560
560 KW at 240/480V, 3-ph.
420 KW at 208/416V, 3-ph.
374 KW at 240V, 1-ph.
Electra-660
660 KW at 240/480V, 3-ph.
495 KW at 208/240V, 3-ph.
440 KW at 240V, 1-ph.
Voltage
Dual: 240/480V
AC, 3-ph. Operational at any voltage to 480V AC max., 1-ph. or
3-ph.
Frequency
50, 60, 400
Hertz
Load Step Resolution
5KW
Fan/Control Power
230/460V,
3-ph., 60Hz
190/380V, 3-ph., 50Hz
Switchable internal (generator) - external
230/460-115V control power transformer internal to Load Bank
15' external power cord
Connection
3-wire plus
ground
Fault Rating
200,000 AIC
Insulation Rating
600V, 302°F
Duty Cycle
Continuous
Ambient Air Temp.
120°F
max.
Dimensions
32 W
x 72.25 H x 60 D
Weight
1,675 lbs.
Enclosure
NEMA-1 drip
proof
Options
Remote control
cables
Weatherproof Cover
NEMA-3R weatherproof configuration of Electra enclosure. Includes
hinge-open protective door with safety interlock over air-exhaust
outlet.
Highway Trailer
Complimentary Load Banks to increase capacity:
650 KW auxiliary resistive load bank with 50 KW load step resolution,
dual voltage
550 KW, 450 KW, as above
345 KVAR (Electra-460), 420KVAR (Electra-560), or 495KVAR (Electra-660);
3.75 KVAR load step resolution, dual voltage
Total load current transformer bank. Permits system of Electra
plus auxiliary load banks to be metered from panel of Electra
Centralized control of system of Electra plus auxiliary load
banks
Click here for a complete
list of options available for Large Portable Load Banks.
Sales
Bulletin
Dimensions
and
Key Features Diagram
|
|
|
|
Powr-Web Load
Element

Simplex Load Banks utilize the
UL Recognized, Powr-Web load element. The Powr-Web
is an advanced design, air-cooled power resistor specifically
designed for application to load bank systems. The Powr-Web
is conservatively operated at half the maximum temperature rating
of the alloy and features a short-circuit-safe design based on
continuous mechanical support of the resistor by high temperature,
ceramic clad stainless steel rods. The Power Webs
are assembled into discrete trays which are assembled in a vertical
stack. Each tray in the stack is independently
serviceable without disturbing adjacent trays.
 |
Ratings
3333W at 120V
4170W at 139V
8333 watt 240/480V
16,777 watt at 480V
Specifications
Alloy: FeCrAl
Max. continuous temp. rating: 1920°F
Maximum operating temperature as applied in Load Bank: 1080°
F
Cool down time from operating to ambient temperature: 10 seconds

Construction
Calibrated to specific
ohm value
Welded lugs on each end
All load elements are continuously supported by vibration resistant,
ceramic clad, stainless steel throughrods
|
Branch Circuit Fuse Protection
The load of a Resistive Load
Bank consists of a dense array of open, uninsulated power resistors
mounted within a cooling air stream. Since the elements are electrically
live, it is possible for a foreign object to penetrate the element
array and create a short circuit of adjacent elements or a short
to ground. Since the elements are densely packed, it is possible
for a short circuit, once started, to rapidly propagate through
the entire element array. As a Load Bank represents a relatively
large amount of power concentrated within a relatively small
volume, a self-propagating, cascading short circuit would have
catastrophic results.
Simplex virtually eliminates
the dangers of short circuit through the use of branch circuit
fuse protection of the load elements. Per NEC 110-10, protective
devices shall clear a fault without extensive damage
to the circuit components. A Simplex Load Bank is divided into
branch circuits of not more than 50 KW each.
|
|
|
ELECTRA
PORTABLE LOAD BANK
|
 |
CAPACITY,
KW (1.0 P.F.) |
COOLING SYSTEM |
|
MODEL |
480V,
3-PH. |
416V,
3-PH. |
380V,
3-PH. |
240V,
3-PH. |
208V,
3-PH. |
240V,
1-PH. |
HP |
CFM |
CHANGE OF TEMP. |
|
NOM. |
MAX. |
|
Electra 460 |
460 |
345 |
288 |
460 |
345 |
307 |
3.0 |
9,000 |
153°F |
290°F |
|
Electra 560 |
560 |
420 |
351 |
560 |
420 |
374 |
3.0 |
10,500 |
160°F |
325°F |
|
Electra 660 |
660 |
495 |
414 |
660 |
495 |
440 |
5.0 |
12,500 |
158°F |
350°F |
ELECTRA
PORTABLE LOAD BANK
LOAD STEP DETAIL
|
|
KW EACH STEP
(1.0 P.F) |
|
QUANTITY |
480V, 3-PH. |
416V, 3-PH. |
480V, 3-PH. |
240V, 3-PH. |
208V, 3-PH. |
240V, 1-PH. |
|
1 |
5 |
3.75 |
3.1 |
5 |
3.75 |
3.3 |
|
1 |
10 |
7.5 |
6.3 |
10 |
7.5 |
6.7 |
|
1 |
20 |
15 |
12.6 |
20 |
15 |
13.3 |
|
1 |
25 |
18.75 |
16 |
25 |
18.75 |
16.7 |
|
2 |
50 |
37.5 |
31 |
50 |
37.5 |
33.3 |
|
3-4-5 |
100 |
75 |
63 |
100 |
75 |
66.7 |
|