Large
Portable

Load Cube
2500KW

Request Quote
 

Load Cube
Portable Load Bank

The Simplex Load Cube is an ultra-large capacity, fully portable, resistive/reactive Load Bank System intended for field use in testing, maintenance and performance proving of large generating systems. The Load Cube is rated 2500KW, 1875KVAR at 400-600V commercial AC voltages. The Load Cube is typically used to test large diesel generators, turbines, paralleled generators and shipboard generators.

With a purpose-built design consisting of rugged, all-welded, tubular steel frame, heavy gauge steel sides, guarded hinged doors, power-operated ventilation louvers, the Load Cube is far superior to designs which use refurbished and modified ISO shipping containers. Four-sided access allows ready service of all components and facilitates the ultra-compact design.

Compact and easily transportable, the Load Cube is ideal for rental use. With a footprint of only 8 x 10 feet and a height of less than 9 feet, the Load Cube is easily transportable by conventional-height flat bed trailer. Lifting eyes and forklift channels simplify site movement.

Local Control PanelThe Load Cube utilizes digital load control for direct access of load values, block transitions, and user programmable automation. A selection of digital power meters and data acquisition software is available.

The Simplex Load Cube represents the ultimate technology in large generator load testing performance.

Powr-Web Load Elements

Load Elements

Simplex Powr-Web:
Open wire, helically wound, chromium alloy, load element thermally derated to 60%. 5% tolerance, 2% balance. .995 p.f. Element wire mechanically supported over entire length such that if a wire should break, the broken wire segments will not short to adjacent conductors or to ground. Load elements are individually serviceable and replaceable in the field without major disassembly of the load bank. The load elements are installed in slide-out, removable trays such that any element is easily accessed without disturbing any other elements.

All materials used in the mounting and installation of the load elements are suitable for the temperatures encountered, in both normal operation and under fault conditions.Materials in direct contact with the element wire are ceramic. Other materials which structurally support the load elements and/or which form the hot air duct within which the elements are mounted are steel, stainless steel or aluminum. Plastics and glass reinforced plastic materials and flammable materials are not used for installation, support and mounting of load elements or in the construction of the load bank hot air duct.

Inductive Elements:
Non-saturable, air-gap type, iron-core power inductors. 5% tolerance, 1% waveform distortion, 0.05 power factor, 150°C rise, 220°C insulation.


Simplex Load Banks can be used to satisfy the requirements of the National Fire Protection Association (NFPA) for emergency stand-by power systems.

Load Cube Large Portable Load Bank


Branch Circuit FusesUtilizes the UL Recognized, “Powr-Web” load element

Branch circuit fuse protection of load elements

Inductive load elements
 

Load Cube Large Portable Load Bank

The Load Bank is a completely self-contained, freestanding unit which includes all resistive load elements, load control devices, load element branch circuit fuse protection, main load bus and terminals, cooling system, control power supply, unit controller and malfunction detection system and NEMA type enclosure.


Features

Portable, self-contained: lifting eyes, forklift channels, heavy skid base, and suitable for direct transport by standard flat bed truck

Horizontal airflow

Intake and exhaust louvers with linear actuator power operator and protective screen

Four-sided service access via hinged doors with lockable, flush latches

Power cable connection behind hinge-up door. Cables connect to full rated copper bus bar

Control connection to plug-in connectors located within recessed side well

NEMA3R weatherproof construction suitable for all-weather transport and use

PLC based digital control with remote operator interface terminal:
direct access digital load control and user programmable automatic load control

Data acquisition system (optional): digital power meter and data acquisition software for use with user supplied PC

Tray mounted resistive load elements

Rack mounted inductive load elements

Forced air interior cooling


System Protection

Sensors, alarms (alarm message on remote operator interface terminal), lock-outs as appropriate, for the following:

Fan failure, each of two fans

High exhaust temperature,
each of two fans

High intake temperature

High interior temperature,
sensed at three points

Louver open/closed,
each of eight louvers
SPECIFICATIONS

Capacity
3125KVA, 0.8 p.f.;
2500KW, resistive;
1875KVAR, inductive

Voltage
Nominal, 480V AC, 3-phase, 3-wire, to 600V, 50–60 Hertz

Frequency
60 Hertz, 50 Hertz available

Load Steps
Digital load control, 10 kw, 7.5 kvar resolution. Circuits of 10–20–20–50–100–100–200–250–250–500–1000 KW
7.5–15–15–37.5–75–75–150–187.5–187.5–375–750KVAR

Control Power
Internal, derived from power source under load. 480-3-60V AC.
Control circuits at 120V via internal isolation transformer.
Fan motor load: 2 x 10HP, 13A.
Control power load: 3.0 KVA, 6.25A.

Duty Cycle
Continuous

Ambient Temperature
125°F

Exhaust Rise
220°F

Airflow
Approx 60,000 cfm divided between two cooling fans

Basic Dimensions
96.5”W x 110.25”H x 130”D

Load Control
Branch circuit contactors, each 50KW resistive circuit max or each 75KVAR inductive circuit max. Inductive circuits are double-break. Contactors have enclosed silver surfaced contacts, 120V coils; electrically operated and electrically held.

Element Circuit Protection
Branch circuit fuses, each 50KW resistive branch circuit max, each 75kvar inductive branch circuit max. 600v, 200KAIC, current limiting type.

Power Wiring
150°C insulated; color-coded and numbered.

Control Wiring
105°C

Power Connection
Plated bus bar behind hinge-up access door.

Control Connection
Connector plugs with recessed protective well.

Cooling
Forced air, horizontal airflow. 2 x 10HP, 3-phase, TEFC motor direct driving cast aluminum fan blades. Circuit breaker combination motor starter.

Enclosure
NEMA3R control section; NEMA3R power section. Epoxy primed, polyurethane finish coating, dark gray. Power operated ventilation louvers. Lifting eyes, forklift channels, hinged, lockable, access doors with flush latches.

Sales Bulletin
 
Dimensions and
Key Features Diagram

 

Optional Suitcase-Style Remote Controller

Load Bank Control

Remote digital load control and data acquisition

PLC based load control with remote operator interface control

Direct access digital load control in increments of 10kw, 7.5 kvar

Operator programmable automatic test routines

Digital Power Meter with data acquisition software