Large
Portable
dynaMITE
310KW
290KW
217KW
208KW

|
dynaMITE 300
Portable Load Bank
The Simplex dynaMITE 300
Portable Load Bank provides highly versatile load-test capability
for the manufacturers, distributors and users of small-to-medium
size AC power systems to 300KW nominal.
The dynaMITE 300 is suitable for production line, service
shop or field testing of engine generators, UPS systems, ground
power units, auxiliary power units, static inverters or virtually
any other AC power source. This load bank can be applied to all
common AC voltages to 480V maximum, 50-60-400Hz, single or 3-phase.
The dynaMITE 300 is a fully self-contained test instrument
which includes test instrumentation, connection cables, high
capacity cooling system, rugged load elements, complete load
application control devices, and automatic system protection
devices.
The dynaMITE 300 is compact and fully portable and includes
lifting eyes, forklift channels, and moving handles. Connection
cables are conveniently stowed in a cable compartment behind
a hinged door. All instruments and controls are protected by
hinged panel covers.

|

Features
Portable, compact, self-contained
Broad voltage capability
Fine load step resolution
Utilizes the UL Recognized Powr-Web
load element
Branch circuit
fuse protection of load elements
Toggle switch control of load steps
Complete test instrumentation and system fault protection
Fused control power circuits
Fan motor circuit breaker
Connection cables included
Fast set-up, quick turnaround
Field use capable
|
SPECIFICATIONS
Capacity
315KW at 480V,
3-ph.
290KW at 240V, 3-ph.
217KW at 208V, 3-ph.
208KW at 240V, 1-ph.
Voltage
Operator
selectable:
High: 250-480V AC, 3-ph.
Low: 12-240V AC, 1-ph. or 3-ph.
Frequency
50, 60, 400
Hertz
Load Step Resolution
1KW
Fan/Control Power
User selectable:
External
120V AC, 1-ph., 60Hz, 20A
Internal
240V AC, 1-ph., 60Hz, 3W
240V AC, 3-ph., 60Hz, 4W
120V AC, 1-ph., 60Hz, 2W
Optional Internal, above plus:
480V AC, 3-ph., 50, 60Hz
Airflow
8,000 CFM
Temperature Rating
120°F
max. intake
275°F max. exhaust
Duty Cycle
Continuous
Net Weight
800 lbs.
Dimensions
32 W
x 48 H x 60 D
Enclosure
NEMA-1 drip
proof
Options
KW meter
Running time meter
1% accuracy digital panel meters
Digital power meter
Extended terminal power capability (to 480V, 3-ph., 60Hz)
400Hz instruments
Remote control provision
Companion Load Bank
Vinyl cover
Weatherproof enclosure
Highway trailer
Click here for a complete list of
options available for Large Portable Load Banks.
Sales
Bulletin
Dimensions
and
Key Features Diagram
|
|
|
|
AC Meters, 3½,
+/- 2%
Voltmeter, 0-600V, 50-60Hz
Ammeter, 0-250/1000A
Combination Volt-ammeter Switch
Frequency Meter, Direct Reading (Dial)
Type 45-65 Hz
Voltage Selector Switch
(12-240V/250-480V)
Fan/Control Power Switch
Load Control Switches
Master Load Application Switch
Load Step Switches
|
Normal Operation
Neon Indicator Light
Internal Fan/Control Power Available Neon Indicator
Light
Failure Detection System, Neon Alarm Lights and Lockout
Fan Failure
High Intake Temperature
High Exhaust Temperature
Overvoltage
|
|
Simplex Load Banks can
be used to satisfy the requirements of the National Fire Protection
Association (NFPA) for emergency stand-by power systems. |
|
|
|
DYNAMITE
300 PORTABLE LOAD BANK
CAPACITY DETAIL
|
|
Voltage (AC) |
480V, 3-PH. |
416V, 3-PH. |
380V, 3-PH. |
240V, 3-PH. |
208V, 3-PH. |
240V, 1-PH. |
|
KW (1.0 P.F.) |
315 |
238 |
197 |
289 |
217 |
208 |
DYNAMITE
300 PORTABLE LOAD BANK
LOAD STEP DETAIL
|
|
KW
EACH STEP (1.0 P.F) |
|
QUANTITY |
480V,
3-PH. |
416V,
3-PH. |
480V,
3-PH. |
240V,
3-PH. |
208V,
3-PH. |
240V,
1-PH. |
|
1 |
- |
- |
- |
1.25 |
.94 |
.84 |
|
1 |
- |
- |
- |
2.5 |
1.9 |
1.7 |
|
1 |
5 |
3.75 |
3.1 |
5 |
3.75 |
3.4 |
|
1 |
10 |
7.5 |
6.3 |
10 |
7.5 |
6.7 |
|
1 |
20 |
15 |
12.6 |
20 |
15 |
13 |
|
3 |
40 |
30 |
25 |
40 |
30 |
26 |
|
2 |
80 |
60 |
50 |
80 |
60 |
52 |
|