Electra
Portable Load Bank

The Simplex Electra is a very large capacity, high performance Portable Load Bank designed to provide the manufacturers, distributors and users of large AC generators and UPS systems with sophisticated testing capability.

The Electra provides 460KW, 560KW or 660 of resistive load at both 240V and 480V, 3-phase. It can be applied at any AC voltage to 480V AC, 50-60-400 Hertz, single or 3-phase. Load step resolution is 5KW.

The Electra is a totally self-contained testing system. It includes all resistive load elements, load control devices, load element circuit protective devices, connection cable set, cooling system, malfunction detection system, control power supply and test instrumentation.


Principal Sub-Systems

Load Elements: Simplex “Powr-Web” chromium alloy, open wire, continuously supported, power resistor.

Load Control: 3-Pole magnetic contactors.

Load Element Circuit Protection: Branch circuit fuses. One set of fuses each 50KW branch. Fuses are current limiting type, 200,000 AIC, 600V, enabling safe use on large generating or UPS system.

Cooling System: 3-phase, direct-drive fan, 12,500 CFM.

Malfunction Detection System: Protection against fan failure, high exhaust air temperature, high intake air temperature, overvoltage and fan reversal.

Control Power Supply: Dual voltage control power transformer with supply power switchable to internal (generator) or external.

Test Instrumentation: 3½”, +/- 2% accuracy panel meters. Options available.

Remote Control: Load control switch panel removable for remote operation. Connection plugs will accept optional remote control cables.

Connection: 12’ connection cable set including 3-phase power cables, ground cable and external control power cord, stored behind hinged door in rear compartment.

Control Panel

AC instrumentation, 3½”, +/- 2% accuracy panel meters:
AC voltmeter with 3-ph. transfer switch
AC ammeter with 3-ph. transfer switch
Frequency meter

Load step control toggle switches

Master load control toggle switch

Control power switch

Voltage selector switch

Fan reversal switch

Operational indicator lights
:
Normal Operation
Overvoltage
Fan failure/over temperature

 

Electra 560 Large Portable Load Bank

Features

High capacity, dual voltage

Fine load step resolution

Toggle switch load control

Utilizes the proven Simplex “Powr-Web” load element


Branch circuit fuse protection of load elements

Totally self-contained

Fan/control power-source is operator selectable:

Internal Power: Fan and control circuits powered internally, does not require external power

External Power: Fan and control circuits powered from external 3-phase outlet or other external source

Integral high capacity cooling fan

3-phase connection cable set stowed in cable compartment

Compact, rugged, portable enclosure

Double wall construction for cool exterior

Control compartments thermally insulated from load elements

Hinge-open control panel doors

Comprehensive automatic malfunction detection system with alarm lights

Test instrumentation

Remote control capability

Simplex Load Banks can be used to satisfy the requirements of the National Fire Protection Association (NFPA) for emergency stand-by power systems.

 
Electra 560 Large Portable Load Bank control panel
SPECIFICATIONS

Capacity
Electra 460
460 KW at 240/480V, 3-ph.
345 KW at 208/416V, 3-ph.
307 KW at 240V, 1-ph.

Electra-560
560 KW at 240/480V, 3-ph.
420 KW at 208/416V, 3-ph.
374 KW at 240V, 1-ph.

Electra-660
660 KW at 240/480V, 3-ph.
495 KW at 208/240V, 3-ph.
440 KW at 240V, 1-ph.

Voltage
Dual: 240/480V AC, 3-ph. Operational at any voltage to 480V AC max., 1-ph. or 3-ph.

Frequency
50, 60, 400 Hertz

Load Step Resolution
5KW
 
Fan/Control Power
230/460V, 3-ph., 60Hz
190/380V, 3-ph., 50Hz
Switchable internal (generator) - external
230/460-115V control power transformer internal to Load Bank
15' external power cord

Connection
3-wire plus ground

Fault Rating
200,000 AIC

Insulation Rating
600V, 302°F

Duty Cycle
Continuous

Ambient Air Temp.
120°F max.

Dimensions
32” W x 72.25” H x 60” D

Weight
1,675 lbs.

Enclosure
NEMA-1 drip proof

Options

Remote control cables

Weatherproof Cover

NEMA-3R weatherproof configuration of Electra enclosure. Includes hinge-open protective door with safety interlock over air-exhaust outlet.

Highway Trailer

Complimentary Load Banks to increase capacity:
650 KW auxiliary resistive load bank with 50 KW load step resolution, dual voltage
550 KW, 450 KW, as above
345 KVAR (Electra-460), 420KVAR (Electra-560), or 495KVAR (Electra-660); 3.75 KVAR load step resolution, dual voltage

Total load current transformer bank. Permits system of Electra plus auxiliary load banks to be metered from panel of Electra

Centralized control of system of Electra plus auxiliary load banks

Click here for a complete list of options available for Large Portable Load Banks.
 

Sales Bulletin

Dimensions and
Key Features Diagram

 
 


ELECTRA PORTABLE LOAD BANK
 

CAPACITY, KW (1.0 P.F.)

COOLING SYSTEM

MODEL

480V,
3-PH.

416V,
3-PH.

380V,
3-PH.

240V,
3-PH.

208V,
3-PH.

240V,
1-PH.

HP

CFM

CHANGE OF TEMP.

NOM.

MAX.
Electra 460 460 345 288 460 345 307

3.0

9,000

153°F

290°F

Electra 560

560

420

351

560

420

374

3.0

10,500

160°F

325°F

Electra 660

660

495

414

660

495

440

5.0

12,500

158°F

350°F


ELECTRA PORTABLE LOAD BANK
LOAD STEP DETAIL

 
KW EACH STEP (1.0 P.F)
QUANTITY 480V, 3-PH. 416V, 3-PH. 480V, 3-PH. 240V, 3-PH. 208V, 3-PH. 240V, 1-PH.
1 5 3.75 3.1 5 3.75 3.3
1 10 7.5 6.3 10 7.5 6.7
1 20 15 12.6 20 15 13.3
1 25 18.75 16 25 18.75 16.7
2 50 37.5 31 50 37.5 33.3
3-4-5 100 75 63 100 75 66.7

Back to Load Bank Main Page
 