|
Engineers Specifications
for Stationary Load Banks
(Freestanding,
Forced Air)

|
Options in the specifications
are italicized within parenthesis. Blanks are provided
in section 1.3.1 and 1.3.3 for the addition of specific values.
1. Generator Load Bank
1.1 General: A UL listed, air-cooled,
resistive Load Bank is required for permanent, on site installation
as a component of a standby/emergency power engine generator
system. The Load Bank is to be used for periodic, scheduled,
supervised maintenance exercise and testing of the standby/emergency
power source. The Load Bank shall be operated in (remote or
local), (automatic or manual) control.
1.2 Installation: The Load Bank shall be installed
(outdoors or indoors) on a concrete pad. (The indoor
Load Bank installation shall include an air duct for the Load
Bank hot air exhaust. This duct shall be sized to produce a back
pressure of not more than 1/3 inch water column. The duct shall
be vented to the outdoors.)
1.3 Load Bank
Rating:
1.3.1 Load
Capacity: _____ KW, 1.0 p.f.
1.3.2 Load steps as a minimum: 1/4, 1/2, 3/4, full.
1.3.3 Voltage: _____ V AC, (1 phase, 2-wire
or 3 phase, 3-wire)
1.3.4 Frequency: (60, 50 or 400) Hertz
1.3.5 Ambient Temperature: 120°F maximum
1.3.6 Duty Cycle: Continuous
1.4 Load Bank
Design
1.4.1 General:
The Load Bank shall be a completely self-contained, freestanding
unit which includes all resistive load elements, load control
devices, load element branch circuit fuse protection, main load
bus and terminals, cooling system, unit controller and malfunction
detection system and NEMA type enclosure.
1.4.2 The Load Bank shall be the manufacturer's standard
product that has been investigated, tested and listed by Underwriters
Laboratories as a system for the purpose intended. Simple assemblies
of listed parts that are not system UL listed shall not be acceptable.
1.4.3 Enclosure: The Load Bank enclosure shall be NEMA
type (3R or 1), designed for (outdoor or indoor)
installation on a concrete pad.
1.4.3.1 (Load Banks installed indoors shall include
a duct flange adaptor or accept an exhaust duct supplied by the
installing contractor. The indoor installation shall include
a hot air exhaust duct which will vent all exhaust air to the
outdoors.)
1.4.3.2 The Load Bank enclosure shall be of double
wall construction for cool exterior and thermal isolation of
the load elements.
1.4.3.3 Cooling airflow through the enclosure shall be
vertical with cold air intake at the bottom and hot air exhaust
out the top. Intake and exhaust openings shall be screened.
1.4.3.4 All interior spaces of the enclosure shall be
accessible by hinged, lockable doors. Bolt-on panels shall not
be acceptable.
1.4.3.5 The enclosure shall be painted with an industrial
enamel using a UL listed material and process.
1.4.3.6 The enclosure shall include forklift channels
and lifting eyes.
1.4.4 Load Elements: Open, helically wound chromium alloy
electrical resistance wire rated to operate at 60% of the maximum
continuous temperature rating of wire. Element wire to be mechanically
supported over entire length in such a way that should a wire
break, the broken wire segments will not short to adjacent conductors
or to ground.
1.4.4.1 Load elements are to be individually serviceable
and replaceable in the field without major disassembly of the
Load Bank. An acceptable design to satisfy this requirement is
the installation of the load elements in slide-out, removable
trays in such a way that any element is easily accessed without
disturbing any other elements.
1.4.4.2 All materials used in the mounting and installation
of the load elements shall be suitable for the temperatures encountered,
both in normal operation and under fault conditions.
Materials in direct contact with
the element wire shall be ceramic. These ceramics shall be installed
upon and reinforced and supported by stainless steel structures.
Other materials which structurally
support the load elements and/or form the hot air duct within
which the elements are mounted shall be steel, stainless steel
or aluminum.
Plastics and glass reinforced
plastic materials and flammable materials are not acceptable
materials of construction for installation, support and mounting
of load elements or in the construction of the Load Bank hot
air duct.
|
1.4.4.3 Load elements shall be Simplex
"Powr-Web" Brand.
1.4.5 Load Element Short Circuit Protection: The resistive
load shall be fused in branch circuits of not more than 50 KW
each.
1.4.5.1 Load circuit fuses shall be 200,000 A.I.C. current
limiting type, extremely fast acting 600V rated.
1.4.6 Load Control: One magnetic contactor per each fused
branch circuit.
1.4.7 Load Bank Power Wiring: 150°C insulated.
1.4.8 Main Terminals: Copper, 1000A per square inch.
1.4.9 Cooling System: Forced air cooled by motor drive
propeller fan. Motors shall be (TEFC or ODP), 1800 RPM
maximum and controlled by a circuit breaker combination motor
starter.
1.4.10 Cooling Fan and Control Power: Shall be derived
internally from the main load bus. The cooling fan shall operate
at AC line voltage. Load control circuits and fan motors control
shall operate at 120V and control logic at 24V via control power
isolation transformers. Control circuit fuses shall be 100,000
A.I.C. current limiting type, 600V rated.
1.4.11 Load Bank Controller: The Load Bank shall include
both a local, unit mounted controller and control panel, plus,
if required, a remote control panel. The unit, local controller
shall provide the following functions:
1.4.11.1 Power supply for Load Bank control circuits.
1.4.11.2 Malfunction detection system consisting of sensors
within the Load Bank, Load Bank enable/disable permissive circuit,
and alarms. Malfunction detection sensors to include: cooling
air intake temperature switch set at 120°F, adjustable exhaust
air temperature switch set at not more than 75°F above the
maximum rated temperature rise and an air pressure switch to
sense for loss of cooling airflow.
1.4.11.3 Cooling fan start-stop control.
1.4.11.4 Remote load dump circuit to trip Load Bank off-line
from remote contacts. A manual bypass switch shall be provided
to override the remote contacts.
1.4.11.5 Input/output devices and control circuits for
operation of Load Bank from remote devices when in "automatic"
mode or "remote" mode.
1.4.11.6 Auxiliary dry contacts for field use to indicate
Load Bank "operating normally" and Load Bank "failure."
1.4.11.7 Local, manual control panel consisting of:
Mode selector switch to select
the following:
"Off", "Local-Manual",
"Local-Auto,"
or "Remote"
Manual "Run" and "Stop"
buttons
Switch to bypass remote load dump
contacts
Master load control switch
Load step control switches,
one for each load step
Lamp rest push-button
1.4.11.8 Status annunciator with visual
indicators for the following:
Power connected to Load Bank
Load Bank running in local-manual
mode
Load Bank running in local-auto
mode
Load Bank running in remote mode
Remote load dump activated
Load dump bypassed
Load Bank operating normally
Load Bank disabled due to cooling
failure
Master load switch on
Load step on
(one for each load step)
1.5 Warranty:
The Load
Bank shall be supplied with a two-year manufacturer's warranty
which covers all materials and service labor. The manufacturer
shall demonstrate the availability of factory service technicians
in support of the Load Bank.
1.6 Start-Up
Service:
The Load Bank manufacturer is to provide one day start-up service
of the Load Bank, on site, after the Load Bank has been installed
and connected.
|
1.7 Qualifications
of Load Bank Manufacturer
1.7.1
The Load Bank shall be a product of a firm regularly engaged
in the design and manufacture of generator Load Banks.
1.7.2 The Load Bank manufacturer shall demonstrate at
least five years experience with at least twenty-five successful
installations of Load Banks similar or equal to the Load Bank
specified herein.
1.7.3 The Load Bank for this application shall be a Simplex
Neptune/Mars/Saturn Series as manufactured by Simplex, Inc. 1139
N. MacArthur Blvd., Springfield, Illinois 62702, 800-637-8603.
Add the following
section in order to include a remote control panel.
1.8 Load Bank
Remote Control Panel
1.8.1
Enclosure shall be NEMA type (1 or 3R), wall mounting,
with hinge-open front.
1.8.2 Terminal blocks shall be provided for connection.
1.8.3 The following functions shall be included:
Mode selector switch to select
the following: "Remote-Manual,"
"Remote-Auto," and "Off."
Manual "Run" and "Stop"
push-buttons
Switch to bypass load dump contacts
Master load control switch
Load step control switches,
one for each load step
Lamp test push-button
1.8.4 Status annunciator with visual indicators for the
following:
Power connected to Load Bank
Load Bank running in remote-manual
mode
Load Bank running in remote-auto
mode
Remote load dump activated
Load dump bypass switch activated
Load Bank operating normally
Load Bank disabled due to cooling
failure
Master load switch on
Load step on
(one for each load step)
1.8.5 Remote control panel shall
be UL listed.
Add the following
section to provide for Load Bank operation as an automatic load
regulator to maintain a preset load level.
1.9 Automatic
Load Bank Controller
1.9.1
The Load Bank is to be equipped with an automatic controller
which will be activated when the Load Bank mode control selector
switch is placed in the "automatic" position.
1.9.2 In Automatic mode, the Load Bank is to be on-line
and continuously operative whenever the power source runs. The
Load Bank shall provide a component of the total power source
load and shall be automatically variable in response to dynamic
total load demands upon the power source.
1.9.3 The automatic controller shall include control logic,
solid-state sensors and time delays which shall act to apply/remove
Load Bank component in multiple steps in response to dynamic
output of the power source.
1.9.4 The automatic controller shall function to maintain
total load upon the power source within a preset bandwidth by
adding Load Bank load component as external load component drops
and removing Load Bank component as external load rises.
1.9.5 The automatic controller shall sense load (amperes
or kilowatts).
1.9.6 Full manual control of the Load Bank shall be restored
when the mode selector switch is placed in the "manual"
position.
1.9.7 The automatic controller shall include a solid-state
load sensor with level and time delay adjustment and output contacts
for each load step. A current transformer for external installation
shall be provided.
|