Large
Portable
Merlin
100KW
150KW
200KW
250KW
300KW
350KW
400KW

|
Merlin Portable
Load Bank

|
SPECIFICATIONS
Capacity
100KW, 150KW,
200KW, 250KW, 300KW, 350KW, 400KW
Voltage
High/Low
Mode, operator selectable
High: 250-480V AC, 3-ph.
Low: to 240V AC, single or 3-ph.
Frequency
50, 60, 400
hertz
Fan/Control
Power
User selectable, Internal/External
Internal Control Power
Merlin
100 through Merlin 300
120V, 1-ph., 2w, 60Hz
240V, 1-ph., 3w, 60Hz
208-240V, 3-ph., 4w, 60Hz
Optional: 416-480V, 3-ph., 3w, 60Hz
Optional: 50Hz Voltages
Merlin 300 through Merlin 400
190-205V, 1-ph., 3w, 50Hz
208-240V, 1-ph., 3w, 60Hz
380-416V, 3-ph., 3w, 50Hz
416-480V, 3-ph., 3w, 60Hz
External Control Power
Merlin
100 through Merlin 250
115V, 1-ph., 60Hz, 15A
Merlin 300
115V, 1-ph., 60Hz, 20A
Merlin 350, Merlin 400
230/460V, 3-ph., 50/60Hz, 20A
Cooling
Merlin
100, Merlin 150:
6,000 CFM
Merlin 200 thorugh Merlin 300: 6,700 CFM
Merlin 350, Merlin 400: 8,000 CFM
Duty Cycle
Continuous
Weight
600 lbs. approx.
Dimensions
Merlin
100, Merlin 150
31" W x 47" D x 43" H
Merlin 200 through 300
31" W x 56" D x 50" H
Merlin 350, Merlin 400
31" W x 69" D x 50" H
Sales
Bulletin
Dimensions
and
Key Features Diagram
|
|
Simplex Load Banks can
be used to satisfy the requirements of the National Fire Protection
Association (NFPA) for emergency stand-by power systems. |
|
|
|
The Simplex Merlin is
a dual voltage (240/480V), fine load step resolution, fully instrumented
portable Load Bank intended for shop or field use by engine generator
dealers and service shops for maintenance, testing and performance
proving of engine generator sets, UPS and other power systems
in the 50-400KW range.
The Merlin is a totally self-contained testing system.
It includes all resistive load elements, load control devices,
load element circuit protective devices, connection cable set,
cooling system, malfunction detection system, control power supply
and test instrumentation.
Control Panel
Voltmeter, Ammeter, and Frequency
Meter
Fan Reversal, Volt-Ammeter, Ammeter Range, Load Voltage Selector,
and Control Voltage Selector switches
Fan/Control Power pushbutton
Cooling Failure, Load Over Voltage, and Control Over Voltage
indicator lamps
Master load toggle switch and load step toggle switches |

Hinged Access Door to Fuses and Contactors

Features
Exceptionally rugged, all welded,
formed steel chassis
Utilizes the UL Recognized Powr-Web
load element
Branch
circuit fuse protection of load elements
Lifting eyes, forklift channels and casters
Moving handle
Connection cable set |