Portable

PowerStar
50KW
100KW

Request Quote
 

PowerStar
Portable Load Bank

The Simplex PowerStar Portable Load Bank is an ultra-compact, lightweight, versatile test instrument specially designed for manufacturers, dealers and users of small AC power systems, to 100KW nominal. It is suitable for testing engine generators, wind generators, UPS systems, ground power units, auxiliary power units, static inverters or virtually any other AC power source on the production line, in the service shop or in the field. It can be applied at all common AC voltages to 480V maximum, 50-60-400 Hertz, single or 3-phase.

PowerStar 100 Portable Load Bank Control Panel

At less than 100 pounds and less than seven cubic feet, the PowerStar 50 is highly portable and easily transported to the job site. The Load Bank includes casters, lifting and moving handles. Power connections are plug-in to Cam-Lok connectors. Control and cooling fan power is obtained from a common 115v, 15A outlet via the included connection cord.

The PowerStar is a fully self-contained and portable testing system. It includes integral cooling fans and control circuits, both of which can operate from generator power up to 240V, 60 Hertz (to 480V, 60 Hertz optional). Above 240V or at 50/400 Hertz, the load bank fan and control circuits can be powered from a 15A, 120V wall outlet. An external power cord with plug is included.

The PowerStar control panel includes test instrumentation, load application switches, operation indicator lights and fan/control power switch. The load bank includes rugged “Powr-Web” load elements, load control contactors, branch circuit fuse protection of the load elements, high temperature power wiring, cooling fans with circuit breaker, control power fuses. The load bank is protected against fan failure, high intake air temperature, high exhaust air temperature, and overvoltage. The unit includes Cam-Lok power connectors and a 15' control/fan power cord (115v).

 

PowerStar 100 Portable Load Bank

Features

Lightweight and compact

Portable, self-contained

Branch circuit fuse protection of load elements

Magnetic contactor control of load

Apply/remove load steps in small increments

Use at all common 50, 60 or 400 Hertz voltages, to 480V AC

Digital Power Meter, standard: Volts, Amps, Frequency, Kw

150°C XLP insulated power wiring

Cam-Lok power connectors

Operate fan and control circuits from a common 120V wall outlet, 15' cord provided

Forced air cooled, integral cooling fans

Fan motors protected by fuses

Control circuits fused

Comprehensive malfunction detection system: Overtemperature and fan failure protection; Overvoltage protection

Continuous duty

NEMA-1 enclosure

Casters and handles provided
SPECIFICATIONS

Capacity

50KW, 100KW

Voltage
Dual, nominal 240/480V AC, 3-phase
208-240/416-480V AC, 3-phase, 60Hz
190-220/380-460V AC, 3-phase, 50Hz
110-240V AC, 1-phase, 50-60Hz

Frequency
50–60–400Hz

Fan/Control Power
External, 115V, 1-ph., 60Hz,
15A service, 15' cord with plug provided

Duty Cycle
Continuous

Temp Rating
125° F max intake air temp
Nominal 110° F rise

Power Connection
Cam-Lok connectors,
3xE1016 connectors, #2-y/0, to 400A
Ground = E1015

Cooling Fans
PowerStar 50: 2
PowerStar 100: 4


Dimensions
PowerStar 50: 30" W x 31.5" H x 15" D
PowerStar 100: 30" W x 34" H x 15" D

Options
Running Time Meter
Vinyl Cover
Weatherproof Enclosure
400Hz Meters
400Hz Internal Power
 

Sales Bulletin

Dimensions and
Key Features Diagram

 

Simplex Load Banks can be used to satisfy the requirements of the National Fire Protection Association (NFPA) for emergency stand-by power systems.
 

POWERSTAR PORTABLE LOAD BANK

KW, 1.0 P.F.

LOAD STEPS

MODEL
240/480V,
3-PH.
208/416V,
3-PH.
190/380V,
3-PH.
240V,
1-PH.

KW @ 240/480V,
3-PH.
PowerStar 50

50

37.5

32

33

5, 10, 10, 25
PowerStar 100

100

75

63

67

5, 10, 10, 25, 50

Back to Load Bank Main Page
 

Simplex Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228
800-637-8603 • 217-483-1600 (24 Hr.) • FAX 217-483-1616