Page 22 - SOS Catalog
P. 22

dynaMITE 400R
                                   *
               400KW Digital Load Bank with Data Acquisition
               Page  2






                                                   Options

                                                   •  Network control cables, 25-foot basic   •  12’ connection cable set including
                                                     length                              3-phase power cables, ground cable,
                                                                                         stored in rear compartment
                                                   •  400Hz modification
                                                                                       •  Weather resistant enclosure
                                                   •  Remote control cable extensions
                                                                                       •  Auxiliary inductive load banks with
                                                   •  Simplex AUTO-TEST software for     network control and data capability
                                                     full automation of testing with data
                                                     acquisition and report generation





               Capacity Detail

                                                   FLA                                KW DETAIL
                Model          KW (1.0pf)    240V      480V      240V/480V      208/416V        380V        240V, 1-ph
                dynaMITE 400R     400         961       481         400           300            251           267



               Cooling System

                Model             HP         CFM           T, Nom.        T, Max.
                dynaMITE 400R     3.0       10,500         115°F         300°F





               Voltage: Dual Voltage: 240/480V AC,   Net Weight:                       Digital Load Step Control
               3-phase Operational at any voltage to   1,000 lbs.
               480V AC maximum, single or 3-phase                                      Nominal 5.0 kw resolution: direct enter
                                                                                       any load value and controller will apply
               Frequency: 50, 60 Hertz standard    Control/Fan Power:                  load within nominal 5kw resolution
               Connection: Cam-Type                •  Internal 208-240/416-480V, 3-phase,
                                                     60hz                              Digital Load Calibration
               Time Rating:  Continuous            •  Internal 220/380-416V, 3-phase, 50Hz  Versus Voltage
               Ambient Air Temperature:  120°F max  •  External 208-230/460V, 3-phase,
                                                     60Hz, 11/5.5A                     Controller automatically calibrates loads
               Fault Rating:  200KAIC                                                  for reduced voltage operation.
                                                   •  External 220/380-416V, 3-phase,
               Insulation Rating:  600V, 302°F       50Hz




















               SIMPLEX ONSITE INC.                                                      © 2016 Simplex Onsite, Inc.  All Rights Reserved.
               simplexonsite.com  • 855-SOS-LIVE  • 855-767-5483                        Printed in the USA  •  1409-08.04
               Rental Centers: Springfield, IL; Atlanta; Baltimore; Boston; Denver; Houston; Minneapolis  Design subject to change without notice.




          SOS-dynaMITE-R-1409-08.04.indd   2                                                                         7/14/2016   9:12:58 AM
   17   18   19   20   21   22   23   24   25   26   27