Trident 1250-R

               Digital Load Bank with Data Acquisition
               Rental Duty 600KW - 1250KW  •  Page  2





























               Capacity Detail

                                                    FLA                                 KW DETAIL
                Model         KW (1.0pf)     240V         480V       240V/480V     208/416V      380V       240V, 1-ph*
                Trident 600      600         1444          722          600          450          376          300

                Trident 750      750         1806          903          750          563          470          300
                Trident 800      800         1926          963          800          600          500          300
                Trident 900      900         2166         1083          900          675          564          300
                Trident 1000    1000         2406         1203         1000          750          627          300
                Trident 1250    1250         3008         1504         1250          938          783          300

               *Requires external 3-phase fan/control power. Capacity limited to 1250 FLA.

               Voltage: Dual Voltage: 240/480V AC,   Airflow:  21,000 CFM              Digital Load Control
               3-phase Operational at any voltage to
               480V AC maximum, single or 3-phase  Temperature Rise:  180°F nominal    Nominal 5.0 kw resolution: direct enter
               Optional Voltages: Instead of 240/480v   Control/Fan Power:             any load value and controller will apply
               dual voltage:                       •  230/460V, 3-phase, 60 Hertz      load within nominal 5kw resolution
               a. Any 50hz or 60hz single voltage to 690v  •  190/380V, 3-phase, 50 Hertz  Digital Load Calibration
               b. 600v, single voltage             •  Switchable internal (generator)-   Versus Voltage
               c. 600/480v, dual voltage             external
               d. 600/300v, dual voltage           •  External fan/control power       Controller automatically calibrates loads
               e. 480/416v, dual voltage             requirements: 240/480vAC, 3-phase,   for reduced voltage operation.
                                                     60 Hertz, 40 / 20  amps service
               f.  208/416v, dual voltage            (7.5HP motor)
               Frequency: 50, 60 Hertz standard    •  230/460-115V control power
                                                     transformer internal to Load Bank.
               Connection: 3-wire plus ground
                                                   Net Weight:  Approx. 9500 lbs.,
               Time Rating:  Continuous            including load module, trailer, three
               Ambient Air Temperature:  120°F max  reels, 2000’ 4/0 cable, cam-lock style
                                                   connectors





               SIMPLEX ONSITE INC.                                                      © 2016 Simplex Onsite, Inc.  All Rights Reserved.
               simplexonsite.com  • 855-SOS-LIVE  • 855-767-5483                        Printed in the USA  •  1511-01.00a
               Rental Centers: Springfield, IL; Atlanta; Baltimore; Boston; Denver; Houston; Minneapolis  Design subject to change without notice.




          SOS-Trident-1250-R-1511-01.00a.indd   2                                                                    7/11/2016   1:22:16 PM
   29   30   31   32   33   34   35   36   37   38   39