Page 66 - SOS Catalog
P. 66

LOAD RANGER-R

               Rental Duty 3000KW Load Bank System
               Page  2






               The Load Bank is a completely self-                                     Dimensions and
               contained, freestanding unit which                                      Key Features
               includes all resistive load elements,
               load control devices, load element
               branch circuit fuse protection, main
               load bus and terminals, cooling system,
               control power supply, unit controller and
               malfunction detection system.
               System Protection

               Sensors, alarms (alarm message on
               operator interface terminal), lock-outs as
               appropriate, for the following:
               •  Fan failure, each of two fans
               •  High exhaust temperature, each of
                 two fans
               •  High intake temperature
               •  High interior temperature
               •  Louver open/closed



















               Load Elements                       Power Connection                    Enclosure
               Simplex Powr-Web: Open wire,
               helically wound, chromium alloy, load   Bolt on bus bar and cam-lock style   Type 3R control section; Type 3R power
               element thermally derated to 60%. 5%   connectors behind hinge-up access   section. Epoxy primed, polyurethane
               tolerance, 2% balance. .995 p.f. Element   door.                        finish coating, dark gray. Power
               wire mechanically supported over                                        operated exhaust ventilation louvers.
               entire length such that if a wire should   Cooling                      Lifting eyes, forklift channels, hinged,
               break, the broken wire segments will                                    lockable, access doors with flush
               not short to adjacent conductors or to   Forced air, vertical airflow. 2 x 10HP,   latches.
               ground. Load elements are individually   3-phase, TEFC motor direct driving cast
               serviceable and replaceable in the field   aluminum fan blades. Circuit breaker
               without major disassembly of the load   combination motor starter.
               bank. The load elements are installed
               in slide-out, removable trays such that
               any element is easily accessed without
               disturbing any other elements.










               SIMPLEX ONSITE INC.                                                      © 2016 Simplex Onsite, Inc.  All Rights Reserved.
               simplexonsite.com  • 855-SOS-LIVE  • 855-767-5483                        Printed in the USA  •  1606-10.00
               Rental Centers: Springfield, IL; Atlanta; Baltimore; Boston; Denver; Houston; Minneapolis  Design subject to change without notice.




          SOS-LoadRanger-R-1606-10.00.indd   2                                                                       7/11/2016   1:31:10 PM