Rental Duty                                               ATLANTIS-500R
                     Low Voltage Load Bank
                               to 600v                                                    Water-Cooled Load Bank









                  Overview

                  •  500KW Water-Cooled Load Bank
                  •  Compact, space-efficient design with
                    casters
                  •  Totally quiet operation
                  •  Suitable for use with chilled-water
                    systems in data centers
                  •  Digital control with portable
                    touchscreen
                  •  Power transducer, V-A-Hz-KW display
                    on screen
                  Description

                  The Atlantis-Series is an attractive
                  alternative to air-cooled Load Banks: it
                  is perfectly quiet and cool running; it is
                  extremely compact and may be installed
                  in otherwise unutilized space; it is
                  virtually maintenance free.
                  The Atlantis-500 is ideal for data center
                  chiller system commissioning. With its
                  large 4-inch water connections and
                  minimal pressure drop, the Atlantis will
                  accept the high water flows required for
                  limited temperature rise, typically 12.5°F.
                  Multiple Atlantis Load Banks can be
                  networked to form large systems     Control power for the Load Bank
                  controlled from a single operator   is provided by 120V, transformer
                  interface. In addition, the Atlantis   isolated, internal power supplies.
                  shares the same control architecture   Control power is derived internally,
                  with the Simplex Nautilus-250, 250kw   from the connected power source
                  water-cooled load bank, permitting   or from an external source.
                  any number of Atlantis and Nautilus
                  Load Banks to be networked together.   Power distribution within the
                  Control and data acquisition software   Load Bank is via a 3-phase
                  is available from Simplex for systems   main copper load bus. Field
                  integration and for control from PC’s.  connections are via cam-lok type
                                                      connectors.
                  Each load cell includes sensors for
                  normal operation, cooling failure,   The Atlantis 500 is suitable for use
                  overpressure and loss of flow / low   with a variety of cooling media,
                  water level.                        including city water (nominal
                                                      50 PSI), closed loop chilled
                  Load elements are water immersion   water systems, heat exchanger
                  power resistors. Load control is via   systems, pumped water from
                  magnetic contactors with branch circuit   natural sources (lake, river, etc.)
                  power fuses.                        or brine or sea water (requires
                                                      optional nickel alloy construction
                                                      and elements).