  Trident 150KW-1250KW Load Bank Overview

Simplex Load Banks - Trident Stationary Load Bank

Very-high capacity load testing of generators or electric dynamometer testing of large engines and turbines is achieved with the Simplex Trident Load Bank. The unit capacity range of the Trident is 150KW-1250KW, resistive, unity power factor. The Trident may be used singly or in systems of multiple units which yield total capacities of tens or hundreds of megawatts. Pictured is a 2000KW system (two Tridents) with customer specified paint. Reactive units (inductive or capacitive) are also available.

The Trident is a single or dual voltage Load Bank suitable for all common 50-60-400 hertz voltages up to 600V.

  Trident 150KW-1250KW Load Bank Features

General
Simplex Trident load banks can be used to satisfy the requirements of the National Fire Protection Association (NFPA) for emergency stand-by power systems.
Load Elements
Elements mounted in easily accessible, slide out trays.
Simplex Powr-Web chromium alloy, open wire, continuously supported, power resistor.
UL Recognized.
System Controls
Standard: Simplex D-Series Digital Controller with local or remote touchscreen.
Cooling
Integral forced air cooling system.
3-phase, direct drive motor.
Rain shedding exhaust hood.
Forced air, horizontal airflow -- cold air intake, hot air exhaust.
Malfunction Protections
Sensors, alarms (alarm messages and exhaust temperature displays on touchscreen), lock-outs as appropriate, for the following: fan failure, high exhaust temperature and high intake temperature.
Load Circuit Protection: branch circuit fuses. One set of fuses each 50KW branch. Fuses are current limiting type, 200,000 AIC, 600V, enabling safe use on large generating or UPS system.
Load Control
Branch circuit contactors each step or each 50KW circuit maximum.
Contactors with enclosed silver surfaced contacts, 120V coils; electrically operated and electrically held.
Connections
Control Wiring: 105°C, color coded.
Power Wiring: 150°C XLP color-coded.
Cables connect to full rated copper bus bar with an oversized terminal junction box.
Cables connectable through top or bottom of chassis.
Enclosure
Type 3R weatherproof power section, including load elements and cooling fan.
Type 3R weatherproof control section, thermally and electrically isolated from resistive load power section.
Double wall construction for cool exterior.
Service access from three sides via hinged doors with lockable latches.
Finish painted with a UL Listed process consisting of either a powder-coated finish or a liquid-coated finish consisting of an epoxy primer and a polyurethane finish.