  Saturn-HV Medium Voltage Load Bank Overview

Simplex Load Banks - Saturn-HV Stationary Load Bank

The Saturn-HV is a self-contained Load Bank to 15KV utilizing the Simplex Saturn Load Module with on-board dry-type power transformer. It is a freestanding, skidded unit consisting of three principle sections:

1. High voltage section consisting of main input power terminals, high voltage: 480V 3-phase power transformer, low voltage output terminals, and outputs to load cell.
2. 480V, low voltage resistive load section consisting of one 1500KW-3000KW forced air-cooled load cell.
3. Control Section.

  Saturn-HV Medium Voltage Load Bank Features

General
Simplex Saturn-HV load banks can be used to satisfy the requirements of the National Fire Protection Association (NFPA) for emergency stand-by power systems.
Load Elements
Simplex Powr-Web chromium alloy, open wire, continuously supported, power resistor.
Elements mounted in slide-out trays.
UL Recognized
System Controls
Standard: Simplex D-Series Digital Controller with local or remote touchscreen.
Cooling
Integral forced air cooling system.
Ultra-high volume forced air cooling system.
Air temperature rise limited to 150-200°F range.
Vertical airflow -- cold air intake at bottom, hot air exhaust at top.
Water shedding exhaust hood.
System Protections
Sensors, alarms (alarm message on remote operator interface terminal), lock-outs as appropriate, for the following: fan failure, high exhaust temperature and high intake temperature).
Load Circuit Protection: branch circuit fuses. One set of fuses each 50KW branch. Fuses are current limiting type, 200,000 AIC, 600V, enabling safe use on large generating or UPS system.
Load Control
Master load toggle switch and load step toggle switches.
Branch circuit contactors, each 50KW step.
Contactors with enclosed silver surfaced contacts, 120V coils; electrically operated and electrically held.
Power
Control Wiring: 105°C, color coded.
Power Wiring: 105°C.
Cables connect to full rated copper bus bar with an oversized terminal junction box.
Enclosure
Type 3R weatherproof power section, including load elements and cooling fan.
Type 3R weatherproof control section, thermally and electrically isolated from resistive load power section.
Double wall construction for cool exterior.
Exhaust hood mounts atop power section. Hood may be deleted and a duct flangee provided for indoor application where air is exhausted through a duct to the outdoors.
Service access from three sides via hinged doors with lockable latches.
Enclosure abrasively blasted or chemically etched, primed and finished.
Anti-condensation heaters at 120V, 1ø, 240V 1ø, or any common 3ø voltage.
Transformer
Dry trype transformer
1500-3000KVA, continuous duty
High voltage delta, 3-wire primary
480V wy, 4-wire secondary with grounded neutral
220°C insultation / 150°C rise